Plan Review Notes
Plan Review Notes For Permit 18100526
Permit Number 18100526
Review Stop M
Sequence Number 3
Notes
Date Text
2020-03-26 14:14:573RD REVIEW FBC-2017 MECHANICAL
 PERMIT- 18100526
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 FBC FS 107.2.1- INFORMATION AND CONSTRUCTION DOCUMENTS
 SHEET A1.420- SHOWS THE BEACH CLUB, PLEASE SHOW THE
 LOCATION OF THIS BEACH CLUB. PLEASE PROVIDE SPEC.
 SHEETS ON ALL THE COOKING EQUIPMENT. PLEASE SHOW WHY A
 HOOD SYSTEM IS NOT REQUIRED FOR THIS COMMERCIAL
 KITCHEN. THE HOOD SYSTEM WILL REQUIRE A SEPARATE PERMIT
 WITH DRAWINGS. ALSO SHOW ANY MECHANICAL SYSTEM FOR THE
 BEACH CLUB.
 SHEET A1.403: PLEASE PROVIDE INFORMATION ON CHEMICALS
 AND QUANTITIES OF POOL CHEMICALS.
 MISSING MECHANICAL SHEETS: M2.02G, M2.03N, M2.03S.
 SHEET M2.01S: PLEASE IDENTIFY THE CLOUDED REVISION 2.
 SHEET M2.01S AND SHEET M2.02G ARE THE SAME SHEET.
  
 SHEET- M2.01N:
 1) PROVIDE VENTILATION CALCULATIONS FOR THIS ENTIRE
 BUILDING.
 2) SHOW CFM?S OF THE 48X24 FRESH AIR LOUVER AND THE
 CAPACITY OF THE 20X12 FRESH AIR DUCT.
 3) SHOW THE CFM?S OF THE 36X24 VENTILATION LOUVER FOR
 THE LOADING AREA.
 4) PLEASE PROVIDE THE CFM?S OF ALL RETURN REGISTERS.
 5) ONCE CFM?S OF RETURNS ARE LABELED ON ALL SHEETS
 PLEASE MAKE SURE THAT EACH ROOM?S SUPPLY AND RETURN AIR
 IS BALANCED.
 6) PLEASE PROVIDE A FSD FOR ALL DUCTS PENETRATING THE 2
 HOUR FIRE BARRIERS OF THE CORRIDOR. FBC M- 607.5.2.1
 HORIZONTAL EXITS.
 7) ALL MECHANICAL SHEETS WILL NEED A DIGITAL SEAL AND
 SIGNATURE FROM THE LICENSED DESIGNER. FBC FS
 FAC61G15-23.004.
 8) PLEASE IDENTIFY THE 2 RECTANGULAR PIECES ARE ON THE
 CEILING OF THE LOADING AREA.
 9) RETURN AIR DUCT FOR UNIT HP-N1.4 WILL NEED A FD AT
 THE FIRE PARTITION PENETRATION FOR THE CORRIDOR WALL.
 10) THE SUPPLY DUCT FOR HP-N1.4 NEEDS A FD.
  
  
 ALL UPPER FLOORS:
 1) THE OAR IS SUPPLYING 50 CFM OF AIR IN EACH OF THE
 ELECTRICAL ROOMS, HOW ARE YOU EXHAUSTING THIS AIR?
 2) THE SEF HAS A TOTAL CAPACITY OF 2500 CFM, PLEASE
 SHOW HOW MUCH AIR THE SER IS EXHAUSTING ON EACH FLOOR.
 3) OAR IS SUPPLYING 40CFM OF AIR TO THE TRASH ROOM ON
 EACH FLOOR, HOW ARE YOU EXHAUSTING THIS AIR?
 4) PLEASE SHOW VENTILATION OF THE TRACH COMPACTOR AREA.
  
  
 SHEET M2.01S:
 1) PROVIDE VENTILATION CALCULATIONS FOR THIS ENTIRE
 BUILDING.
 2) SHOW CFM?S OF THE 48X24 FRESH AIR LOUVER AND THE
 CAPACITY OF THE 20X12 FRESH AIR DUCT
 3) SHOW THE CFM?S OF THE 36X24 VENTILATION LOUVER FOR
 THE LOADING AREA.
 4) PLEASE PROVIDE THE CFM?S OF ALL RETURN REGISTERS.
 5) ONCE CFM?S OF RETURNS ARE LABELED ON ALL SHEETS
 PLEASE MAKE SURE THAT EACH ROOM?S SUPPLY AND RETURN AIR
 IS BALANCED.
 6) PLEASE PROVIDE A FSD FOR ALL DUCTS PENETRATING THE 2
 HOUR FIRE BARRIERS OF THE CORRIDOR.
 7) ALL MECHANICAL SHEETS WILL NEED A DIGITAL SEAL AND
 SIGNATURE FROM THE LICENSED DESIGNER.
 8) PLEASE IDENTIFY THE 2 RECTANGULAR PIECES ARE ON THE
 CEILING OF THE LOADING AREA.
 9) YOU CALL OUT AN OA INTAKE LOUVER FOR THE FCC ROOM
 BUT IT IS NOT SHOWN ON THE DRAWING.
 10) RETURN AIR DUCT FOR UNIT HP-S1.4 WILL NEED A FD AT
 THE FIRE PARTITION PENETRATION FOR THE CORRIDOR WALL.
 11) THE SUPPLY DUCT FOR HP-S1.4 NEEDS A FD
  
  
  
 ALL UPPER FLOORS:
 1) THE OAR IS SUPPLYING 50 CFM OF AIR IN EACH OF THE
 ELECTRICAL ROOMS, HOW ARE YOU EXHAUSTING THIS AIR?
 2) THE SEF HAS A TOTAL CAPACITY OF 2500 CFM, PLEASE
 SHOW HOW MUCH AIR THE SER IS EXHAUSTING ON EACH FLOOR.
 3) OAR IS SUPPLYING 40CFM OF AIR TO THE TRASH ROOM ON
 EACH FLOOR, HOW ARE YOU EXHAUSTING THIS AIR?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  