| 2020-03-26 14:14:57 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 18100526 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | FBC FS 107.2.1- INFORMATION AND CONSTRUCTION DOCUMENTS |
| | SHEET A1.420- SHOWS THE BEACH CLUB, PLEASE SHOW THE |
| | LOCATION OF THIS BEACH CLUB. PLEASE PROVIDE SPEC. |
| | SHEETS ON ALL THE COOKING EQUIPMENT. PLEASE SHOW WHY A |
| | HOOD SYSTEM IS NOT REQUIRED FOR THIS COMMERCIAL |
| | KITCHEN. THE HOOD SYSTEM WILL REQUIRE A SEPARATE PERMIT |
| | WITH DRAWINGS. ALSO SHOW ANY MECHANICAL SYSTEM FOR THE |
| | BEACH CLUB. |
| | SHEET A1.403: PLEASE PROVIDE INFORMATION ON CHEMICALS |
| | AND QUANTITIES OF POOL CHEMICALS. |
| | MISSING MECHANICAL SHEETS: M2.02G, M2.03N, M2.03S. |
| | SHEET M2.01S: PLEASE IDENTIFY THE CLOUDED REVISION 2. |
| | SHEET M2.01S AND SHEET M2.02G ARE THE SAME SHEET. |
| | |
| | SHEET- M2.01N: |
| | 1) PROVIDE VENTILATION CALCULATIONS FOR THIS ENTIRE |
| | BUILDING. |
| | 2) SHOW CFM?S OF THE 48X24 FRESH AIR LOUVER AND THE |
| | CAPACITY OF THE 20X12 FRESH AIR DUCT. |
| | 3) SHOW THE CFM?S OF THE 36X24 VENTILATION LOUVER FOR |
| | THE LOADING AREA. |
| | 4) PLEASE PROVIDE THE CFM?S OF ALL RETURN REGISTERS. |
| | 5) ONCE CFM?S OF RETURNS ARE LABELED ON ALL SHEETS |
| | PLEASE MAKE SURE THAT EACH ROOM?S SUPPLY AND RETURN AIR |
| | IS BALANCED. |
| | 6) PLEASE PROVIDE A FSD FOR ALL DUCTS PENETRATING THE 2 |
| | HOUR FIRE BARRIERS OF THE CORRIDOR. FBC M- 607.5.2.1 |
| | HORIZONTAL EXITS. |
| | 7) ALL MECHANICAL SHEETS WILL NEED A DIGITAL SEAL AND |
| | SIGNATURE FROM THE LICENSED DESIGNER. FBC FS |
| | FAC61G15-23.004. |
| | 8) PLEASE IDENTIFY THE 2 RECTANGULAR PIECES ARE ON THE |
| | CEILING OF THE LOADING AREA. |
| | 9) RETURN AIR DUCT FOR UNIT HP-N1.4 WILL NEED A FD AT |
| | THE FIRE PARTITION PENETRATION FOR THE CORRIDOR WALL. |
| | 10) THE SUPPLY DUCT FOR HP-N1.4 NEEDS A FD. |
| | |
| | |
| | ALL UPPER FLOORS: |
| | 1) THE OAR IS SUPPLYING 50 CFM OF AIR IN EACH OF THE |
| | ELECTRICAL ROOMS, HOW ARE YOU EXHAUSTING THIS AIR? |
| | 2) THE SEF HAS A TOTAL CAPACITY OF 2500 CFM, PLEASE |
| | SHOW HOW MUCH AIR THE SER IS EXHAUSTING ON EACH FLOOR. |
| | 3) OAR IS SUPPLYING 40CFM OF AIR TO THE TRASH ROOM ON |
| | EACH FLOOR, HOW ARE YOU EXHAUSTING THIS AIR? |
| | 4) PLEASE SHOW VENTILATION OF THE TRACH COMPACTOR AREA. |
| | |
| | |
| | SHEET M2.01S: |
| | 1) PROVIDE VENTILATION CALCULATIONS FOR THIS ENTIRE |
| | BUILDING. |
| | 2) SHOW CFM?S OF THE 48X24 FRESH AIR LOUVER AND THE |
| | CAPACITY OF THE 20X12 FRESH AIR DUCT |
| | 3) SHOW THE CFM?S OF THE 36X24 VENTILATION LOUVER FOR |
| | THE LOADING AREA. |
| | 4) PLEASE PROVIDE THE CFM?S OF ALL RETURN REGISTERS. |
| | 5) ONCE CFM?S OF RETURNS ARE LABELED ON ALL SHEETS |
| | PLEASE MAKE SURE THAT EACH ROOM?S SUPPLY AND RETURN AIR |
| | IS BALANCED. |
| | 6) PLEASE PROVIDE A FSD FOR ALL DUCTS PENETRATING THE 2 |
| | HOUR FIRE BARRIERS OF THE CORRIDOR. |
| | 7) ALL MECHANICAL SHEETS WILL NEED A DIGITAL SEAL AND |
| | SIGNATURE FROM THE LICENSED DESIGNER. |
| | 8) PLEASE IDENTIFY THE 2 RECTANGULAR PIECES ARE ON THE |
| | CEILING OF THE LOADING AREA. |
| | 9) YOU CALL OUT AN OA INTAKE LOUVER FOR THE FCC ROOM |
| | BUT IT IS NOT SHOWN ON THE DRAWING. |
| | 10) RETURN AIR DUCT FOR UNIT HP-S1.4 WILL NEED A FD AT |
| | THE FIRE PARTITION PENETRATION FOR THE CORRIDOR WALL. |
| | 11) THE SUPPLY DUCT FOR HP-S1.4 NEEDS A FD |
| | |
| | |
| | |
| | ALL UPPER FLOORS: |
| | 1) THE OAR IS SUPPLYING 50 CFM OF AIR IN EACH OF THE |
| | ELECTRICAL ROOMS, HOW ARE YOU EXHAUSTING THIS AIR? |
| | 2) THE SEF HAS A TOTAL CAPACITY OF 2500 CFM, PLEASE |
| | SHOW HOW MUCH AIR THE SER IS EXHAUSTING ON EACH FLOOR. |
| | 3) OAR IS SUPPLYING 40CFM OF AIR TO THE TRASH ROOM ON |
| | EACH FLOOR, HOW ARE YOU EXHAUSTING THIS AIR? |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |