2020-01-07 17:29:33GAS 2ND REVIEW **DENIED**18100526
  
 1) ALL APPLIANCE AND EQUIPMENT INSTALLATION MANUALS ARE
 REQUIRED TO BE SUBMITTED FOR PLAN REVIEW. THIS IS
 SOMETHING THAT CAN NOT BE DEFERRED. WPB AMEND
 107.3.4.1, 107.3.5.1.4
 2) RESPONSE DOES NOT CLARIFY ON WHY A L.P SIZING AND
 NAT GAS SIZING CHARTS WAS SUBMITTED. PLEASE CLARIFY AND
 SUBMIT THE CORRECT CHARTS. FBC 107.2.1. WHAT GAS TYPE
 IS THIS SYSTEM? FBC 107.2.1
 3)SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF
 CORRUGATED STAINLESS STEEL TUBING.(IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
  
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH