| Plan Review Notes For Permit 18100526 |
| Permit Number |
18100526 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-01-07 17:29:33 | GAS 2ND REVIEW **DENIED**18100526 | | | | | | 1) ALL APPLIANCE AND EQUIPMENT INSTALLATION MANUALS ARE | | | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW. THIS IS | | | SOMETHING THAT CAN NOT BE DEFERRED. WPB AMEND | | | 107.3.4.1, 107.3.5.1.4 | | | 2) RESPONSE DOES NOT CLARIFY ON WHY A L.P SIZING AND | | | NAT GAS SIZING CHARTS WAS SUBMITTED. PLEASE CLARIFY AND | | | SUBMIT THE CORRECT CHARTS. FBC 107.2.1. WHAT GAS TYPE | | | IS THIS SYSTEM? FBC 107.2.1 | | | 3)SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF | | | CORRUGATED STAINLESS STEEL TUBING.(IF APPLICABLE) FOR | | | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1 | | | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 | | | | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | | | | | | | | | | |
|