| Date |
Text |
| 2019-11-21 16:42:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | THE FOLLOWING COMMENTS REGARDING FIRE SPRINKLER |
| | PROTECTION REQUIRE ADDITIONAL REVIEW AND DISCUSSION. |
| | |
| | IN AN EFFORT TO MOVE THIS PROJECT FORWARD THEY ARE |
| | BEING PROVISOED AND BE ADDRESSED DURING SHOP DRAWING |
| | DEVELOPMENT AND DESIGN. |
| | |
| | CLOSE COORDINATION WITH THE OFFICE OF THE FIRE MARSHAL |
| | IS STRONGLY ENCOURAGE TO AVOID SHOP DRAWING DELAYS. |
| | |
| | 17) SHEET 6.067 - CANOPIES ARE NOTED ON BOTH TOWERS |
| | WITH LIMITED DETAIL. THERE APPEARS TO BE NO FIRE |
| | SPRINKLER PROTECTION UNDER THEM. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.7* EXTERIOR PROJECTIONS. |
| | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| | OR |
| | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR |
| | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE |
| | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| | THAT |
| | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| | RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703. |
| | 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM BELOW |
| | THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| | PROVIDED |
| | THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| | ARE NONCOMBUSTIBLE, |
| | LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| | WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| | PROJECTIONS CONTAIN |
| | ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| | FOLLOWING |
| | UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| | (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| | NONCOMBUSTIBLE |
| | INSULATION |
| | (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| | TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| | ENCLOSED |
| | JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| | INCLUDING |
| | SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| | WITHIN |
| | THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| | [SEE |
| | 11.2.3.1.4(4)(D)] |
| | (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| | PROJECTIONS |
| | NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| | 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM |
| | EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE |
| | CORRIDOR |
| | ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS |
| | ENTIRELY |
| | OF NONCOMBUSTIBLE CONSTRUCTION. |
| | 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR |
| | PROJECTIONS |
| | GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
| | COMBUSTIBLES |
| | ARE STORED. |
| | |
| | WHAT IS THE CONSTRUCTION TYPE, FRAME AND COVER? |
| | |
| | THE CANOPIES SHALL BE SUBMITTED UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND NOTE OF SEPARATE |
| | PERMIT. |
| | |
| | |
| | |
| | 18) SHEET A 3.104 - THERE APPEARS TO BE THREE 4' |
| | BALCONIES ON EACH TOWER AT THE GARAGE TOP FLOOR THAT |
| | WILL HAVE VEHICLES PARKED UNDER THEM. THERE DOES NOT |
| | APPEAR TO BE FIRE SPRINKLER PROTECTION ON THE UNDERSIDE |
| | OF THE BALCANY. |
| | |
| | 8.15.7* EXTERIOR PROJECTIONS. |
| | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| | OR |
| | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR |
| | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE |
| | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| | THAT |
| | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| | RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703. |
| | 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM BELOW |
| | THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| | PROVIDED |
| | THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| | ARE NONCOMBUSTIBLE, |
| | LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| | WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| | PROJECTIONS CONTAIN |
| | ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| | FOLLOWING |
| | UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| | (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| | NONCOMBUSTIBLE |
| | INSULATION |
| | (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| | TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| | ENCLOSED |
| | JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| | INCLUDING |
| | SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| | WITHIN |
| | THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| | [SEE |
| | 11.2.3.1.4(4)(D)] |
| | (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| | PROJECTIONS |
| | NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| | 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM |
| | EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE |
| | CORRIDOR |
| | ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS |
| | ENTIRELY |
| | OF NONCOMBUSTIBLE CONSTRUCTION. |
| | 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR |
| | PROJECTIONS |
| | GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
| | COMBUSTIBLES |
| | ARE STORED. |
| | |
| | PLEASE REVIEW AND CORRECT, VEHICLES ARE CONSIDERED |
| | COMBUSTIBLE STORAGE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |