Plan Review Notes
Plan Review Notes For Permit 18100526
Permit Number 18100526
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-11-21 16:42:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 THE FOLLOWING COMMENTS REGARDING FIRE SPRINKLER
 PROTECTION REQUIRE ADDITIONAL REVIEW AND DISCUSSION.
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD THEY ARE
 BEING PROVISOED AND BE ADDRESSED DURING SHOP DRAWING
 DEVELOPMENT AND DESIGN.
  
 CLOSE COORDINATION WITH THE OFFICE OF THE FIRE MARSHAL
 IS STRONGLY ENCOURAGE TO AVOID SHOP DRAWING DELAYS.
  
 17) SHEET 6.067 - CANOPIES ARE NOTED ON BOTH TOWERS
 WITH LIMITED DETAIL. THERE APPEARS TO BE NO FIRE
 SPRINKLER PROTECTION UNDER THEM.
  
 PER NFPA 13
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703.
 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW
 THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION,
 PROVIDED
 THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS
 ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED
 WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR
 PROJECTIONS CONTAIN
 ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE
 FOLLOWING
 UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE
 INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED
 TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE
 ENCLOSED
 JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME,
 INCLUDING
 SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR
 WITHIN
 THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC
 [SEE
 11.2.3.1.4(4)(D)]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS
 NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM
 EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE
 CORRIDOR
 ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS
 ENTIRELY
 OF NONCOMBUSTIBLE CONSTRUCTION.
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 WHAT IS THE CONSTRUCTION TYPE, FRAME AND COVER?
  
 THE CANOPIES SHALL BE SUBMITTED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND NOTE OF SEPARATE
 PERMIT.
  
  
  
 18) SHEET A 3.104 - THERE APPEARS TO BE THREE 4'
 BALCONIES ON EACH TOWER AT THE GARAGE TOP FLOOR THAT
 WILL HAVE VEHICLES PARKED UNDER THEM. THERE DOES NOT
 APPEAR TO BE FIRE SPRINKLER PROTECTION ON THE UNDERSIDE
 OF THE BALCANY.
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703.
 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW
 THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION,
 PROVIDED
 THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS
 ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED
 WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR
 PROJECTIONS CONTAIN
 ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE
 FOLLOWING
 UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE
 INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED
 TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE
 ENCLOSED
 JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME,
 INCLUDING
 SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR
 WITHIN
 THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC
 [SEE
 11.2.3.1.4(4)(D)]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS
 NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM
 EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE
 CORRIDOR
 ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS
 ENTIRELY
 OF NONCOMBUSTIBLE CONSTRUCTION.
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 PLEASE REVIEW AND CORRECT, VEHICLES ARE CONSIDERED
 COMBUSTIBLE STORAGE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  