Plan Review Notes
Plan Review Notes For Permit 18100526
Permit Number 18100526
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-12 06:16:11PLUMBING 1ST REVIEW **DENIED**18100526** SEE COMMENTS
 ON FOUNDATION PERMIT#18100522 AND ADDRESS THOSE
 COMMENTS ON THIS SET OF PLANS AS WELL AS NEEDED.
  
 1)YOU CALL OUT 2 INTERCEPTORS STRIEM SETTLER ON SHT.
 P6.06 AND A 100 GALLON SCHIER OS-100 ON SHT. P4.01N
 NOTE #5 THAT I HAVE NOT BEEN ABLE TO LOCATE LOCATION
 AND WHAT IT WILL SERVE. PLEASE CLARIFY,. FBC 107.2.1
 2)NONE OF THE PLUMBING SHEETS ARE DIGITALLY SIGNED AS
 REQUIRED FAC 61G15-23.001, 61G15-23.005
 3)P4.01N CALLS OUT FBC-PLB 708.3.4 REQUIRING CLEAN OUTS
 AT THE BASE OF EVERY STACK. THIS SECTION WAS REMOVED
 FOR THE LATEST EDITION. THIS JOB IS UNDER THE 2017 FBC
 6TH EDITION PLEASE REMOVE THIS NOTE AS IT MAY CAUSE
 CONFUSION WITH FIELD WORKERS.
 4)SHT P4.04N ON THE ISOMETRIC YOU SO THE USE OF AAV?S.
 AAV?S BELOW THE 4TH LEVEL BRANCH INTERVAL ARE NOT
 PERMITTED. FBC-PLB 918.3.1
 5)SHT. P5.07S IT APPEARS THE DISTANCE FROM THE HOT
 WATER SOURCE DEVELOPED LENGTH IS MORE THEN 50? TO THE
 FURTHEST FIXTURE. PLEASE CONFIRM DISTANCE OR CHANGE
 WATER ISOMETRIC TO BE CODE COMPLAINT.
 6) PROVIDE TUB/SHOWER AND ROMAN TUB VALVES SHOWING TEMP
 LIMITED TO 120F MAX AND MEET FBC-PLB 424.5 WITH VALVE
 CONFORMS TO ASSE 1016.
 7)LIFT STATION AND ALL OTHER BACKFLOWS SHALL BE LEAD
 FREE, INSTALLED BY A PLUMBING CONTRACT, A SEPARATE
 PERMIT, AND ALL SHALL BE PVB. F.S 489 AND WPB CROSS
 CONNECTION MANUAL 2017. PVB BACK
 8) SHT.A0.200 UNDER GENERAL REQUIREMENTS YOU LIST 2017
 FBC ACCESSIBILITY AND 2010 ADA STANDARD. THE 2010 ADA
 STANDARD IS THE BASE CODE THAT THE FLORIDA
 ACCESSIBILITY IS BASED ON BUT THIS BUILDING WILL BE
 STICKLEY UNDER THE REQUIREMENTS SET FORTH IN THE 2017
 6TH ED FLORIDA ACCESSIBILITY CODE. PLEASE REMOVE THE
 2010 ADA STANDARD AS IT MAY CAUSE CONFUSION. FBC
 107.2.1
 9)A0.200 NOTE #68 CALL FOR ALL DRINKING FOUNTAINS TO BE
 MOUNTED MAX 36?. FBC-PLB 410.3 REQUIRED A HI-LOW
 DRINKING FOUNTAIN. 36? WOULD NOT MEET FBC-ACC 602.7 FOR
 A STANDARD HEIGHT PERSON. PLEASE CORRECT
 10)A0.200 NOTE #76 CALLS FOR THE MIRROR MOUNTED MAX 40?
 TO THE BOTTOM EDGE. FBC-ACC 603.3 REQUIRED THE
 MEASUREMENT BE 40? TO THE REFLECTIVE SURFACE.
 11)A0.200 NOTE #77 CALLS FOR THE PAPER DISPENSER 12?
 FROM THE FRONT EDGE OF THE TOILET. THE REQUIREMENT
 CALLED OUT IN FBC-ACC 604.9, 309.4 IS 7?-9? FROM THE
 FRONT EDGE OF THE TOILET TO THE CENTER OF THE
 DISPENSER.
 12) A0.200 NOTE #92 CALLS FOR ONLY THE HOT WATER AND
 DRAIN LINE BE PROTECTED AGAINST CONTACT. FBC-ACC 606.5
 REQUIRED ALL PIPING TO INCLUDE THE COLD WATER PIPING BE
 PROTECTED.
 13) A0.200 UNDER GENERAL LAVATORIES PLEASE ADD THAT ALL
 PUBLIC HAND SINKS SHALL BE TEMPERED TO MAX 110F BY AN
 APPROVE ASSE 1070 DEVICE.
 14)A0.200 FIGURE #35 SHOWS ROLL IN SHOWER AND APPEARS
 THE ENTIRE BACK WALL IS APPROVED TO MOUNT THE CONTROL
 VALVES. WITH THIS SHOWER HAVING A SEAT THE CONTROL WALL
 IS THE BACK BUT VALVE IS LIMITED TO BE WITH IN 27? FROM
 THE SEAT. FBC-ACC 608.5.2
 15)A6.301 THE TRASH CHUTE IN NOTE #10 CALLS OUT FOR A
 SANITIZING DISINFECTING UNIT. PROVIDE DETAILS FOR THIS
 EQUIPMENT SHOW CONNECTION INTO THE DOMESTIC WATER
 SYSTEM AND BACKFLOW. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  