| 2019-08-12 06:16:11 | PLUMBING 1ST REVIEW **DENIED**18100526** SEE COMMENTS |
| | ON FOUNDATION PERMIT#18100522 AND ADDRESS THOSE |
| | COMMENTS ON THIS SET OF PLANS AS WELL AS NEEDED. |
| | |
| | 1)YOU CALL OUT 2 INTERCEPTORS STRIEM SETTLER ON SHT. |
| | P6.06 AND A 100 GALLON SCHIER OS-100 ON SHT. P4.01N |
| | NOTE #5 THAT I HAVE NOT BEEN ABLE TO LOCATE LOCATION |
| | AND WHAT IT WILL SERVE. PLEASE CLARIFY,. FBC 107.2.1 |
| | 2)NONE OF THE PLUMBING SHEETS ARE DIGITALLY SIGNED AS |
| | REQUIRED FAC 61G15-23.001, 61G15-23.005 |
| | 3)P4.01N CALLS OUT FBC-PLB 708.3.4 REQUIRING CLEAN OUTS |
| | AT THE BASE OF EVERY STACK. THIS SECTION WAS REMOVED |
| | FOR THE LATEST EDITION. THIS JOB IS UNDER THE 2017 FBC |
| | 6TH EDITION PLEASE REMOVE THIS NOTE AS IT MAY CAUSE |
| | CONFUSION WITH FIELD WORKERS. |
| | 4)SHT P4.04N ON THE ISOMETRIC YOU SO THE USE OF AAV?S. |
| | AAV?S BELOW THE 4TH LEVEL BRANCH INTERVAL ARE NOT |
| | PERMITTED. FBC-PLB 918.3.1 |
| | 5)SHT. P5.07S IT APPEARS THE DISTANCE FROM THE HOT |
| | WATER SOURCE DEVELOPED LENGTH IS MORE THEN 50? TO THE |
| | FURTHEST FIXTURE. PLEASE CONFIRM DISTANCE OR CHANGE |
| | WATER ISOMETRIC TO BE CODE COMPLAINT. |
| | 6) PROVIDE TUB/SHOWER AND ROMAN TUB VALVES SHOWING TEMP |
| | LIMITED TO 120F MAX AND MEET FBC-PLB 424.5 WITH VALVE |
| | CONFORMS TO ASSE 1016. |
| | 7)LIFT STATION AND ALL OTHER BACKFLOWS SHALL BE LEAD |
| | FREE, INSTALLED BY A PLUMBING CONTRACT, A SEPARATE |
| | PERMIT, AND ALL SHALL BE PVB. F.S 489 AND WPB CROSS |
| | CONNECTION MANUAL 2017. PVB BACK |
| | 8) SHT.A0.200 UNDER GENERAL REQUIREMENTS YOU LIST 2017 |
| | FBC ACCESSIBILITY AND 2010 ADA STANDARD. THE 2010 ADA |
| | STANDARD IS THE BASE CODE THAT THE FLORIDA |
| | ACCESSIBILITY IS BASED ON BUT THIS BUILDING WILL BE |
| | STICKLEY UNDER THE REQUIREMENTS SET FORTH IN THE 2017 |
| | 6TH ED FLORIDA ACCESSIBILITY CODE. PLEASE REMOVE THE |
| | 2010 ADA STANDARD AS IT MAY CAUSE CONFUSION. FBC |
| | 107.2.1 |
| | 9)A0.200 NOTE #68 CALL FOR ALL DRINKING FOUNTAINS TO BE |
| | MOUNTED MAX 36?. FBC-PLB 410.3 REQUIRED A HI-LOW |
| | DRINKING FOUNTAIN. 36? WOULD NOT MEET FBC-ACC 602.7 FOR |
| | A STANDARD HEIGHT PERSON. PLEASE CORRECT |
| | 10)A0.200 NOTE #76 CALLS FOR THE MIRROR MOUNTED MAX 40? |
| | TO THE BOTTOM EDGE. FBC-ACC 603.3 REQUIRED THE |
| | MEASUREMENT BE 40? TO THE REFLECTIVE SURFACE. |
| | 11)A0.200 NOTE #77 CALLS FOR THE PAPER DISPENSER 12? |
| | FROM THE FRONT EDGE OF THE TOILET. THE REQUIREMENT |
| | CALLED OUT IN FBC-ACC 604.9, 309.4 IS 7?-9? FROM THE |
| | FRONT EDGE OF THE TOILET TO THE CENTER OF THE |
| | DISPENSER. |
| | 12) A0.200 NOTE #92 CALLS FOR ONLY THE HOT WATER AND |
| | DRAIN LINE BE PROTECTED AGAINST CONTACT. FBC-ACC 606.5 |
| | REQUIRED ALL PIPING TO INCLUDE THE COLD WATER PIPING BE |
| | PROTECTED. |
| | 13) A0.200 UNDER GENERAL LAVATORIES PLEASE ADD THAT ALL |
| | PUBLIC HAND SINKS SHALL BE TEMPERED TO MAX 110F BY AN |
| | APPROVE ASSE 1070 DEVICE. |
| | 14)A0.200 FIGURE #35 SHOWS ROLL IN SHOWER AND APPEARS |
| | THE ENTIRE BACK WALL IS APPROVED TO MOUNT THE CONTROL |
| | VALVES. WITH THIS SHOWER HAVING A SEAT THE CONTROL WALL |
| | IS THE BACK BUT VALVE IS LIMITED TO BE WITH IN 27? FROM |
| | THE SEAT. FBC-ACC 608.5.2 |
| | 15)A6.301 THE TRASH CHUTE IN NOTE #10 CALLS OUT FOR A |
| | SANITIZING DISINFECTING UNIT. PROVIDE DETAILS FOR THIS |
| | EQUIPMENT SHOW CONNECTION INTO THE DOMESTIC WATER |
| | SYSTEM AND BACKFLOW. FBC 107.2.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | |