| Plan Review Notes For Permit 18100526 |
| Permit Number |
18100526 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-15 11:33:04 | PLAN DENIED | | | 1) PROVIDE NOA FOR OUTSIDE LOUVERS. | | | 2) LEASING OFFICE SHOWS A 2 HR RATED WALL ON | | | LIFE SAFETY PLAN IF SO FIRE DAMPERS ARE REQUIRED | | | SECTION 607 FBC (M) | | | 3) REFER TO SECTION 504.8.4.1 SPECIFIED LENGTH | | | FOR CLOTHES DRYER EXHAUST. PROVIDE MANUFACTURERS | | | SPECIFICATIONS FOR DRYERS AT FIRST INSPECTION 2017 FBC | | | (M) | | | 4) REFER TO SECTION 403.4.7 SMOKE REMOVAL 2017 FBC | | | HOW IS THE SMOKE REMOVED FROM THE FLOOR OF INCIDENCE. | | | 5) PROVIDE SEQUENCE OF OPERATION FOR THE SMOKE CONTROL | | | AND 1ST FLOOR GARAGE EXHAUST ON PLAN. | | | 6) PAGE A1.420 OF THE PLAN SHOWS A BEACH HOUSE. | | | THE BEACH HOUSE IS NOT ON THE MECHANICAL PLAN. | | | 7) PAGE A1.403 SHOWS CHEMICAL STORAGE. PLEASE | | | PROVIDE MORE INFORMATION ON HOW MUCH AND WHAT | | | CHEMICALS ARE TO BE STORED | | | 8) FAN SCHEDULE PAGE M4.01 SHOWS EMERGENCY POWER | | | REFER TO SECTION 403.4.8.3 STANDBY POWER LOADS # 2 | | | VENTILATION | | | 2017 FBC | | | 9) GENERATOR REQUIRES SEPARATE APPLICATION, PLAN AND | | | PERMIT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|