| 2019-07-02 12:13:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET LS 1.100 - THERE IS AN INCORRECT REFERNCE TO |
| | THE CURRENT LIFE SAFETY CODE. |
| | |
| | PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND CORRECT THE |
| | REFERENCE. |
| | |
| | |
| | |
| | 2) SHEET LS 1.100 - UNDER GENERAL NOTES # 8 THERE ARE |
| | INDICATIONS OF "SHALL CONTAIN" ITEMS. |
| | |
| | PLEASE BE ADVISED THE FOLLOWING LIST IS CONTAINED |
| | WITHIN THE FLORIDA FIRE PREVENTION CODE AND ARE |
| | REQUIRED WITHIN THE COMMAND ROOM |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9.4 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | |
| | A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| | DIMENSION OF 10 FT. |
| | B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS |
| | E. A WORK TABLE. |
| | F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| | SYSTEMS. |
| | J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY |
| | K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | L. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | M. FIRE PUMP STATUS INDICATORS |
| | N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | P. CONTROLS REQUIRED FOR SMOKE CONTROL |
| | Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | AND NFPA 101, CHAPTER 11, |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE |
| | OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 3) SHEET LS 1.100 - UNDER GENERAL NOTES # 9 THERE IS AN |
| | INDICATION OF STANDBY POWER AND REFERENCE TO THE |
| | BUILDING CODE. |
| | |
| | THE INSTALLATION SHALL ALSO COMPLY WITH THE REQUIRMENTS |
| | OF NFPA 37 AND 110. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE |
| | OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) SHEET LS 1.101 AND ALL LS SHEETS - THERE ARE NO |
| | INDICATIONS OF OCCUPANCY LOAD COUNTS AT EACH EXIT DOOR. |
| | |
| | 7.3 CAPACITY OF MEANS OF EGRESS. |
| | 7.3.1 OCCUPANT LOAD. |
| | 7.3.1.1 SUFFICIENT CAPACITY. |
| | 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| | ANY STORY, |
| | BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE |
| | SUFFICIENT FOR THE |
| | OCCUPANT LOAD THEREOF. |
| | 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS, |
| | WHERE MORE |
| | THAN ONE MEANS OF EGRESS IS REQUIRED, THE MEANS OF |
| | EGRESS SHALL BE |
| | OF SUCH WIDTH AND CAPACITY THAT THE LOSS OF ANY ONE |
| | MEANS OF |
| | EGRESS LEAVES AVAILABLE NOT LESS THAN 50 PERCENT OF THE |
| | REQUIRED |
| | CAPACITY. |
| | |
| | 7.3.1.4 EXITS SERVING MORE THAN ONE STORY. WHERE AN |
| | EXIT |
| | SERVES MORE THAN ONE STORY, ONLY THE OCCUPANT LOAD OF |
| | EACH STORY |
| | CONSIDERED INDIVIDUALLY SHALL BE USED IN COMPUTING THE |
| | REQUIRED |
| | CAPACITY OF THE EXIT AT THAT STORY, PROVIDED THAT THE |
| | REQUIRED EGRESS |
| | CAPACITY OF THE EXIT IS NOT DECREASED IN THE DIRECTION |
| | OF EGRESS |
| | TRAVEL. |
| | 7.3.1.5 CAPACITY FROM A POINT OF CONVERGENCE. WHERE |
| | MEANS OF |
| | EGRESS FROM A STORY ABOVE AND A STORY BELOW CONVERGE AT |
| | AN |
| | INTERMEDIATE STORY, THE CAPACITY OF THE MEANS OF EGRESS |
| | FROM THE |
| | POINT OF CONVERGENCE SHALL BE NOT LESS THAN THE SUM OF |
| | THE REQUIRED |
| | CAPACITY OF THE TWO MEANS OF EGRESS. |
| | |
| | PLEASE PROVIDE THE REQUIRED LOADS AT EACH EXIT. |
| | |
| | |
| | 5) LIFE SAFETY SHEETS - THERE ARE INDICATIONS AND |
| | CLACULATIONS OF STAIR CAPACITY LOADS |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.3.2 MEASUREMENT OF MEANS OF EGRESS. |
| | 7.3.2.1 THE WIDTH OF MEANS OF EGRESS SHALL BE MEASURED |
| | IN THE |
| | CLEAR AT THE NARROWEST POINT OF THE EGRESS COMPONENT |
| | UNDER |
| | CONSIDERATION, UNLESS OTHERWISE PROVIDED IN 7.3.2.2 OR |
| | 7.3.2.3. |
| | |
| | THE EXIT CAPACITY OF THE STAIRS SHOULD BE TAKEN FROM |
| | THE NARROWEST POINT, THE EXIT DOOR; HOWEVER, IT IS |
| | SHOWN WITH 0.15. THE FFPC IT IS 0.20. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF |
| | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN |
| | TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FFPC |
| | REFERENCES, THE MOST STRICT SHALL APPLY. |
| | |
| | |
| | |
| | 6) LIFE SAFETY SHEETS - THERE ARE INDICATIONS AND |
| | CLACULATIONS OF STAIR CAPACITY LOADS |
| | |
| | WITHIN THE EXIT LOAD CALCULATION IT IS SHOWING A STAIR |
| | WIDTH OF 48" AND A 0.20 FORMULA. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.3.2 MEASUREMENT OF MEANS OF EGRESS. |
| | 7.3.2.1 THE WIDTH OF MEANS OF EGRESS SHALL BE MEASURED |
| | IN THE |
| | CLEAR AT THE NARROWEST POINT OF THE EGRESS COMPONENT |
| | UNDER |
| | CONSIDERATION, UNLESS OTHERWISE PROVIDED IN 7.3.2.2 OR |
| | 7.3.2.3. |
| | |
| | THE FORMULA SHOULD USE 0.30 |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF |
| | EGRESS SHALL BE BASED ON THE CAPACITY FACTORS SHOWN IN |
| | TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 7) SHEET A 101 - THERE APPEARS TO BE ONLY ONE EXIT FROM |
| | THE POOL DECK AREA. THERE ARE NO LIFE SAFETY PLANS |
| | REGARDING THE POOL DECK. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE POOL DECK |
| | INCLUDING OCCUPANCY LOADS FROM ALL ASSOCIATED EXITS |
| | FROM THE BUILDING INTO IT AND EXITS ACCOUNTING FOR THE |
| | OCCUPANCY LOADS OUT OF IT. |
| | |
| | |
| | |
| | |
| | 8) SHEET LS 1.125 - DOOR T-01 AT STAIR # 1 & # 4 ARE |
| | NOT INDOCATED AS 90 MINUTE LKE RELATED DOORS.(THE DOOR |
| | SCHEDULE INDICATES AS 90 MIN.) |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 9) SHEET LS 1.125 - THERE ARE DOORS WITHIN A RATED WALL |
| | THAT ARE NOT INDICATES AS RATED IN THE DOOR SCHEDULE. |
| | |
| | DOORS N2508A, N2506A, N2506B, N2509B AND N2509C ARE |
| | WITHIN AN INDICATED 2 HOUR WALL AND ARE NOT RATED IN |
| | THE DOOR SCHEDULE NOR THE LIFE SAFETY SHEET. |
| | |
| | PLEASE CORRECT OR JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | OR REVISED WALL RATINGS. |
| | |
| | |
| | |
| | 10) SHEET LS 1.125 - THERE ARE DOORS WITHIN A RATED |
| | WALL THAT ARE NOT INDICATES AS RATED IN THE DOOR |
| | SCHEDULE. |
| | |
| | DOORS S2508A, S2506A, S2506B, S2509B AND S2509C ARE |
| | WITHIN AN INDICATED 2 HOUR WALL AND ARE NOT RATED IN |
| | THE DOOR SCHEDULE NOR THE LIFE SAFETY SHEET. |
| | |
| | PLEASE CORRECT OR JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | OR REVISED WALL RATINGS. |
| | |
| | |
| | |
| | |
| | 11) SHEET A 1.225 NOTH & SOUTH BUILDINGS - THERE ARE |
| | FOUR (4) AREAS INDICATED WITH ACCESS DOORS TO A CRAWL |
| | SPACE FOR THE POOL. |
| | |
| | THE WALL THAT THIS ACCESS DOOR IS LOCATED IS INDCIATED |
| | AS 2 HOURS. |
| | |
| | THERE ARE NO INDICATIONS OF THE RATING OF THE ACCESS |
| | DOOR. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY WITH APPLICABLE |
| | RATED DOORS. |
| | |
| | |
| | |
| | 12) SHEET FP 1.00 - THERE ARE INCORRECT EDITIONS OF |
| | CURRENT FIRE CODES INDICATED. |
| | |
| | THE CORRECT EDITIONS ARE: |
| | |
| | NFPA 13, 2013 EDITION. |
| | NFPA 14, 2013 EDITION. |
| | NFPA 20, 2013 EDITION. |
| | NFPA 24, 2013 EDITION. |
| | |
| | PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 13) SHEET FP 1.00 - NOTE # 14 UNDER FIRE SPRINKLER |
| | NOTES THERE IS AN INDICATION OF UNDERGROUND PIPING. |
| | |
| | ALL UNDERGROUND FIRE LINE SHALL BE INSTALLED PER NFPA |
| | 24 |
| | |
| | |
| | |
| | |
| | 14) SHEET 1.101 - THERE ARE DOORS FROM OCCUPIABLE ROOMS |
| | IN BOTH TOWERS THAT OPEN INTO THE EXIT CORRIDOR THAT |
| | MAY ENCROACH ON THE REQUIRED EXIT WIDTH. |
| | |
| | DOORS S108A, SII3A, SII4A & N107A, N112A, N113A. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED |
| | DIMENSIONS SHOWING COMPLIANCE WITH THE ABOVE CODE. |
| | |
| | |
| | |
| | 15) SHEET 1.101 - STAIRWAY 2 & 3 DISCHARGE INTO THE |
| | POOL AREA; HOWEVER, IT APPEARS TO BE ONE EXIT OUT OF |
| | THE POOL AREA. |
| | |
| | PLEASE PROVIDE A DETAILED OCCUPANCY COUNT, PATH OF |
| | TRAVEL AND TRAVEL DISTANCE, FROM THESE STAIRS , AS WELL |
| | AS, OTHER EXITS INTO THE POOL AREA AND PROVIDE THE |
| | REQUIRED EXIT WIDTH(S) TO A PUBLIC WAY. |
| | |
| | |
| | |
| | 16) SHEET A 1.420 - THE KITCHEN EQUIPMENT PLAN |
| | INDICATES A VENTLESS OPEN FRYER AND RANGE. THOSE |
| | SPECIFICATION SHEETS COULD NOT BE LOCATED. PLEASE |
| | PROVIDE THE SPEC SHEETS AND LISTINGS IN COMPLIANCE WITH |
| | NFPA 96 AND OTHER APPLICABLE CODES. |
| | |
| | 16A) A FIRE SUPPRESSION SYSTEM OF EACH IS REQUIRED AND |
| | SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | |
| | |
| | 17) SHEET 6.067 - CANOPIES ARE NOTED ON BOTH TOWERS |
| | WITH LIMITED DETAIL. THERE APPEARS TO BE NO FIRE |
| | SPRINKLER PROTECTION UNDER THEM. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.7* EXTERIOR PROJECTIONS. |
| | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| | OR |
| | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR |
| | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE |
| | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| | THAT |
| | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| | RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703. |
| | 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM BELOW |
| | THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| | PROVIDED |
| | THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| | ARE NONCOMBUSTIBLE, |
| | LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| | WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| | PROJECTIONS CONTAIN |
| | ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| | FOLLOWING |
| | UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| | (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| | NONCOMBUSTIBLE |
| | INSULATION |
| | (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| | TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| | ENCLOSED |
| | JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| | INCLUDING |
| | SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| | WITHIN |
| | THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| | [SEE |
| | 11.2.3.1.4(4)(D)] |
| | (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| | PROJECTIONS |
| | NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| | 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM |
| | EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE |
| | CORRIDOR |
| | ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS |
| | ENTIRELY |
| | OF NONCOMBUSTIBLE CONSTRUCTION. |
| | 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR |
| | PROJECTIONS |
| | GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
| | COMBUSTIBLES |
| | ARE STORED. |
| | |
| | WHAT IS THE CONSTRUCTION TYPE, FRAME AND COVER? |
| | |
| | THE CANOPIES SHALL BE SUBMITTED UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND NOTE OF SEPARATE |
| | PERMIT. |
| | |
| | |
| | |
| | 18) SHEET A 3.104 - THERE APPEARS TO BE THREE 4' |
| | BALCONIES ON EACH TOWER AT THE GARAGE TOP FLOOR THAT |
| | WILL HAVE VEHICLES PARKED UNDER THEM. THERE DOES NOT |
| | APPEAR TO BE FIRE SPRINKLER PROTECTION ON THE UNDERSIDE |
| | OF THE BALCANY. |
| | |
| | 8.15.7* EXTERIOR PROJECTIONS. |
| | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| | OR |
| | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR |
| | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. |
| | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE |
| | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS |
| | THAT |
| | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE |
| | RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703. |
| | 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM BELOW |
| | THE EXTERIOR PROJECTIONS OF COMBUSTIBLE CONSTRUCTION, |
| | PROVIDED |
| | THE EXPOSED FINISH MATERIAL ON THE EXTERIOR PROJECTIONS |
| | ARE NONCOMBUSTIBLE, |
| | LIMITED-COMBUSTIBLE, OR FIRE RETARDANT?TREATED |
| | WOOD AS DEFINED IN NFPA 703, AND THE EXTERIOR |
| | PROJECTIONS CONTAIN |
| | ONLY SPRINKLERED CONCEALED SPACES OR ANY OF THE |
| | FOLLOWING |
| | UNSPRINKLERED COMBUSTIBLE CONCEALED SPACES: |
| | (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| | NONCOMBUSTIBLE |
| | INSULATION |
| | (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| | NONCOMBUSTIBLE |
| | OR LIMITED-COMBUSTIBLE CEILINGS ARE DIRECTLY ATTACHED |
| | TO THE BOTTOM OF SOLID WOOD JOISTS SO AS TO CREATE |
| | ENCLOSED |
| | JOIST SPACES 160 FT3 (4.5 M3) OR LESS IN VOLUME, |
| | INCLUDING |
| | SPACE BELOW INSULATION THAT IS LAID DIRECTLY ON TOP OR |
| | WITHIN |
| | THE CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC |
| | [SEE |
| | 11.2.3.1.4(4)(D)] |
| | (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR |
| | PROJECTIONS |
| | NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA |
| | 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | FROM |
| | EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF THE |
| | CORRIDOR |
| | ARE AT LEAST 50 PERCENT OPEN AND WHEN THE CORRIDOR IS |
| | ENTIRELY |
| | OF NONCOMBUSTIBLE CONSTRUCTION. |
| | 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR |
| | PROJECTIONS |
| | GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE |
| | COMBUSTIBLES |
| | ARE STORED. |
| | |
| | PLEASE REVIEW AND CORRECT, VEHICLES ARE CONSIDERED |
| | COMBUSTIBLE STORAGE. |
| | |
| | |
| | |
| | 19) SHEETS E - THE EXIT SIGNS IN EACH TOWER'S CORRIDOR |
| | ARE FLAT PARALLEL WITH THE EXIT DOOR AND MAY NOT BE |
| | VISIBLE FROM A DISTANCE. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| | WITHIN AN EXIT |
| | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| | DIRECTIONAL EXIT SIGNS |
| | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| | OBVIOUS. |
| | |
| | PLEASE RELOCATE EXIT SIGNS PERPENDICULAR TO THE |
| | CORRIDOR WITH THE CHEVRON POINTING IN THE DIRECTION OF |
| | THE EXIT DOOR. |
| | |
| | |
| | |
| | 20) SHEETS LS - INDICATIONS OF TACTILE SIGNAGE COULD |
| | NOT BE READILY BE FOUND. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE |
| | SHALL BE |
| | PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS |
| | OTHERWISE |
| | PROVIDED IN 7.10.1.4: |
| | (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR |
| | REQUIRING AN |
| | EXIT SIGN. |
| | (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. |
| | (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, |
| | AMERICAN |
| | NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS |
| | AND |
| | FACILITIES. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 21) STAIRWELL SHEETS - INDICATIONS OF STAIRWAY SIGNAGE |
| | COULD NOT BE READILTY FOUND. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 7.2.2.5.4* STAIRWAY IDENTIFICATION. |
| | 7.2.2.5.4.1 NEW ENCLOSED STAIRS SERVING THREE OR MORE |
| | STORIES AND |
| | EXISTING ENCLOSED STAIRS, OTHER THAN THOSE ADDRESSED IN |
| | 7.2.2.5.4.1(P), SERVING FIVE OR MORE STORIES SHALL |
| | COMPLY WITH |
| | 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(O). |
| | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE |
| | WITHIN THE |
| | ENCLOSURE AT EACH FLOOR LANDING. |
| | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. |
| | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP |
| | AND |
| | BOTTOM OF THE STAIR ENCLOSURE. |
| | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF |
| | THE STAIR |
| | ENCLOSURE. |
| | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND |
| | THE |
| | DIRECTION TO, EXIT DISCHARGE. |
| | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE STAIR |
| | ENCLOSURE. |
| | (G) THE BOTTOM OF THE SIGNAGE SHALL BE LOCATED A |
| | MINIMUM OF 48 |
| | IN. (1220 MM) ABOVE THE FLOOR LANDING, AND THE TOP OF |
| | THE SIGNAGE |
| | SHALL BE LOCATED A MAXIMUM OF 84 IN. (2135 MM) ABOVE |
| | THE FLOOR |
| | LANDING |
| | (H) THE SIGNAGE SHALL BE IN A POSITION THAT IS VISIBLE |
| | WHEN THE |
| | DOOR IS IN THE OPEN OR CLOSED POSITION. |
| | (I) THE SIGNAGE SHALL COMPLY WITH 7.10.8.1 AND 7.10.8.2 |
| | OF THIS |
| | CODE. |
| | (J) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE |
| | IN |
| | ACCORDANCE WITH ICC/ANSI A117.1, AMERICAN NATIONAL |
| | STANDARD |
| | FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES. |
| | (K) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE |
| | WALL OR ON A |
| | SEPARATE SIGN SECURELY ATTACHED TO THE WALL. |
| | (L) THE STAIRWAY IDENTIFICATION SHALL BE LOCATED AT THE |
| | TOP OF THE |
| | SIGN IN MINIMUM 1 IN. (25 MM) HIGH LETTERING AND SHALL |
| | BE IN |
| | ACCORDANCE WITH 7.10.8.2. |
| | (M)* SIGNAGE THAT READS NO ROOF ACCESS SHALL DESIGNATE |
| | STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. LETTERING |
| | SHALL BE A |
| | MINIMUM OF 1 IN. (25 MM) HIGH AND SHALL BE IN |
| | ACCORDANCE WITH |
| | 7.10.8.2. |
| | (N) THE FLOOR LEVEL NUMBER SHALL BE LOCATED BELOW THE |
| | STAIRWAY |
| | IDENTIFIER IN MINIMUM 5 IN. (125 MM) HIGH NUMBERS AND |
| | SHALL BE |
| | IN ACCORDANCE WITH 7.10.8.2. MEZZANINE LEVELS SHALL |
| | HAVE THE LETTER |
| | ?M? OR OTHER APPROPRIATE IDENTIFICATION LETTER |
| | PRECEDING THE FLOOR |
| | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B? |
| | OR OTHER |
| | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR |
| | LEVEL NUMBER. |
| | (O) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF |
| | THE |
| | STAIRWAY SHALL BE ON THE SIGN IN MINIMUM 1 IN. (25 MM) |
| | HIGH |
| | LETTERS OR NUMBERS AND SHALL BE IN ACCORDANCE WITH |
| | 7.10.8.2. |
| | (P) PREVIOUSLY APPROVED, EXISTING SIGNAGE SHALL NOT BE |
| | REQUIRED TO |
| | COMPLY WITH 7.2.2.5.4.1(L) THROUGH (O). |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE |
| | |
| | |
| | |
| | |
| | 22) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 23) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |