| 2019-07-29 14:49:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| | 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 3. IN THE NORTH AND SOUTH GENERATOR ROOM, IT APPEARS |
| | THAT THERE IS A SILENCER IN FRONT OF A TRANSFORMER, AND |
| | THEREFORE THIS TRANSFORMER DOES NOT HAVE THE REQUIRED |
| | CLEARANCE. PROVIDE CLARIFICATION ANDOR CORRECTION. NEC |
| | 110.26 |
| | 4. SHEET E3.02, PROVIDE GFCI PROTECTED RECEPTACLE |
| | OUTLET FOR THE ISLAND. NEC 210.8, 210.52 |
| | 5. SHEET E3.07, E3.08, AND E3.09, PROVIDE GFCI |
| | PROTECTION FOR ALL RECEPTACLE OUTLETS IN LAUNDRY AREA. |
| | NEC 210.8 |
| | 6. FOR ALL DWELLING UNITS, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 7. PROVIDE SELECTIVE COORDINATION, AS APPLICABLE, TO |
| | CONFIRM WITH CODE. NEC 620.62, 695.3(C)(3), 700.28, |
| | 701.27, 708.54 |
| | 8. PANEL SETL SHOWS A 50 AMP MAIN CIRCUIT BREAKER. THE |
| | LOAD FOR THIS PANEL AS SHOWN IN PANEL SEQL IS 73.47 |
| | AMPS. PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16) |
| | 9. PANEL NETL SHOWS A 50 AMP MAIN CIRCUIT BREAKER. THE |
| | LOAD FOR THIS PANEL AS SHOWN IN PANEL NEQL IS 81.27 |
| | AMPS. PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16) |
| | 10. RISER DIAGRAM SHOWS PANELS SM1, SM2, NM1, AND NM2. |
| | LOAD SUMMARY ON SHEET E5.01B SHOWS PANELS MSBS1, MSBS2, |
| | MSBN1, AND MSBN2. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. WPB FBC 107.2.7; NEC 408.4 |
| | 11. UNIT PANELS ARE CURRENTLY SHOWN WITH UNIT TYPE AS A |
| | NAME. PROVIDE BLOCK NOTE THAT THE NAMING OF THESE |
| | PANELS WILL CONFORM TO NEC 408.4. |
| | 12. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 13. PANEL MP DOES NOT SHOW ANY GROUND FAULT PROTECTION |
| | OF CIRCUITS. PROVIDE CLARIFICATION AND/OR CORRECTION. |
| | NEC 210.8, 555.3 |
| | 14. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH |
| | CODE. FBC EC C405.6.3 |
| | 15. SHEET E5.01B STATES THE NORTH AND SOUTH GENERATOR |
| | HAVE AN 800 AMP BREAKER THAT FEEDS ATS-2. THIS TRANSFER |
| | SWITCH IS ONLY RATED FOR 600 AMPS. PROVIDE CORRECTION. |
| | NEC 110.3, 701.4 |
| | 16. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |