| 2019-08-08 10:41:52 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) IT APPEARS FROM THE SITE PLAN AND THE PALM BEACH |
| | COUNTY PROPERTY APPRAISER WEBSITE THAT THE PROJECT |
| | COVERS TWO LOTS. A UNITY OF TITLE IS REQUIRED: |
| | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- |
| | 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF |
| | |
| | 2) PENDING LOMR. THE ELEVATION OF THE LOWEST FINISHED |
| | FLOOR OF THE PROPOSED RESIDENTIAL STRUCTURE DOES NOT |
| | MEET THE REQUIRED BFE AND 2" FREE-BOARD REQUIREMENTS OF |
| | THE CITY OF WEST PALM BEACH'S FLOOD ORDINANCE FOR NEW |
| | STRUCTURES. NOT COMPLIED. PORTIONS OF THE BUILDING ARE |
| | LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE ELEVATIONS |
| | FOR THE PROJECT ARE IN NGVD 88. AS OF OCTOBER 5TH, 2017 |
| | THE CITY OF WEST PALM BEACH HAS ADOPTED NEW FLOOD |
| | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL |
| | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH |
| | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM |
| | OF TWO FEET ABOVE THE BFE. IN ORDER TO AVOID ANY |
| | CONFUSION PLEASE REVISE THE PLANS TO SHOW ONLY THE |
| | CURRENT FLOOD ELEVATION DATA (NAVD 88). ELEVATION |
| | CERTIFICATES WILL BE REQUIRED TO SHOW COMPLIANCE WITH |
| | THE CITY'S FLOOD POLICY. THE CITY REQUIRES THREE |
| | ELEVATION CERTIFICATES. FIRST, A PRECONSTRUCTION ELEV. |
| | CERT. BASED ON THE CONSTRUCTION DRAWING. SECOND, A |
| | CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR |
| | FORMS. THIRD A FINAL ELEV. CERT. BASED ON THE FINISHED |
| | BUILDING. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - |
| | FLOOD PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS |
| | FOR FLOOD HAZARD REDUCTION. |
| | |
| | 3) PENDING. PROVIDE A COPY OF THE PERMIT ISSUED BY THE |
| | ARMY CORPS OF ENGINEERS/EPA TO FILL IN THE 9,610 SQFT |
| | OF SUBMERGED LAND SHOWN ON THE SITE PLAN. FBC 107.2.1 |
| | |
| | 4) THE PROPOSED "DECLARATION" INDICATED IN THE |
| | "TEMPORARY CONSTRUCTION ACCESS EASEMENT AGREEMENT" DOES |
| | NOT ADEQUATELY RESOLVE THE ISSUE OF MAXIMUM ALLOWABLE |
| | AREA OF OPENINGS BASED ON FIRE SEPARATION DISTANCE AND |
| | DEGREE OF OPENING PROTECTION REQUIRED BY FBC TABLE |
| | 705.8. SINCE THE ADJACENT PROPERTY IS NOT UNDER THE |
| | CONTROL OF THE BUILDING OWNER, A RESTRICTIVE COVENT OR |
| | SOME OTHER LEGAL DOCUMENT THAT WILL PREVENT THE |
| | ADJACENT LANDOWNER FROM AMENDING THE EASEMENT SO THAT |
| | THE REQUIRED CLEARANCES ARE MAINTAINED FOR THE LIFE OF |
| | THE BUILDING. NOT COMPLIED. THE PROPERTY TO THE SOUTH |
| | WHERE THE PROPOSED PERMANENT ROADWAY WILL IS NOT UNDER |
| | THE CONTROL OF THIS LANDOWNER. SOME TYPE OF |
| | DOCUMENTATION OF AN EASEMENT OR DEED RESTRICTION |
| | STATING THAT THERE WILL BE A ROADWAY AT THIS LOCATION |
| | IN PERPETUITY WILL NEED TO BE SUBMITTED FOR REVIEW. THE |
| | SOUTH WALL OF THE BUILDING (RESIDENTIAL TOWER AND |
| | PARKING GARAGE) APPEARS TO BE 10 TO 15 FEET FROM THE |
| | PROPERTY LINE AND BASED ON FBC TABLE 705.8 IS LIMITED |
| | TO AN ALLOWABLE AREA 45% OF THE EXTERIOR WALL AREA PER |
| | STORY. SHOW COMPLIANCE WITH FBC 705.8 & TABLE 705.8. |
| | |
| | 5) ON SHEET 00.200 PROJECT DATA, THE 2010 FBC, FIRE |
| | PREVENTION CODE AND ACCESSIBILITY CODE ARE SPECIFIED |
| | AND THE CORRECT REFERENCES FOR THIS PROJECT IS THE 2017 |
| | EDITIONS OF THOSE CODE. FBC CHAPTER 35. |
| | |
| | 6) TWO OF THE EXIT ACCESS STAIRWAYS AND TWO OF THE |
| | GARAGE EMERGENCY EXITS DISCHARGE ONTO THE POOL DECK. BE |
| | AWARE OF THE POOL BARRIER REQUIREMENTS OF FBC |
| | 454.1.3.1.9. |
| | |
| | 7) FBC 403.6.1 REQUIRES TWO FIRE SERVICE ELEVATORS |
| | WHICH ARE REQUIRED TO HAVE A WEIGHT CAPACITY OF NOT |
| | LESS THAN 3,500 LBS. |
| | |
| | 8) FBC 3002.4 REQUIRES AT LEAST ONE PASSENGER ELEVATOR |
| | THAT CAN ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES |
| | BY 76 INCHES IN THE HORIZONTAL OPEN POSITION. |
| | |
| | 9) JUSTIFY THE OCCUPANT LOADS IN THE ASSEMBLY AREAS OF |
| | 15 SQFT PER PERSON IN THE PARTY AREA AND LOBBIES. FBC |
| | 1004.1 |
| | |
| | 10) SHOW THAT THE TWO EXITS FROM THE ROOF POOL DECKS |
| | COMPLY WITH FBC 1007.1.1 FOR EXIT SEPARATION DISTANCE. |
| | |
| | 11) SHOW THE SEPARATION OF EXITS, THE NUMBER OF |
| | OCCUPANTS USING EACH EXIT AND DOOR SIZE WITH CAPACITY |
| | FOR EACH STORY AND EACH AREA REQUIRING TWO OR MORE |
| | EXITS. FBC 1006.2.1, 1007.1 AND 1010.1 |
| | |
| | 12) SHOW THE PATHS OF TRAVEL, EXITS, ETC. FOR THE FIRST |
| | FLOOR OF THE PARKING GARAGE ON THE LIFE SAFETY PLANS. |
| | FBC 1006.2.1, 1017 |
| | |
| | 13) ON SHEET LS1.101G THE GARAGE LIFE SAFETY PLAN FOR |
| | LEVEL 01, DOORS ARE SHOWN FOR THE RESIDENTIAL ACTIVE |
| | USE ROOMS AND THE BIKE PARKING ROOM THAT OPEN DIRRECTLY |
| | INTO A TRAFFIC LANE. HOW WILL THE OCCUPANTS USING THESE |
| | EXITS BE PROTECTED IN THE TRAFFIC AREAS. PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 14) SHOW HOW ACCESS TO BATHROOMS WILL BE PROVIDED THE |
| | RESIDENTIAL ACTIVE USE ROOMS LOCATED AT THE PARKING |
| | GARAGE. FBC 2902, 2902.3.1 & 2902.3.2 |
| | |
| | 15) THE LOCATION OF THE POOL EQUIPMENT ROOM ON SHEET |
| | A1.101 AND SHEET A1.201G ARE NOT THE SAME. PLEASE |
| | COORDINATE THE DRAWINGS. FBC 107.2.1 |
| | |
| | 16) VERIFY THAT THE MINIMUM REQUIRED VERTICAL CLEARANCE |
| | OF 8'-2" IS PROVIDED FOR VAN PARKING SPACES AND ACCESS |
| | ISLES AND THE VEHICULAR ROUTES THAT SERVE THEM. FBC |
| | ACCESSIBILITY 502.5 |
| | |
| | 17) ON SHEET A4.301 WALL SECTION BETWEEN THE BUILDING & |
| | GARAGE THE DISTANCE BETWEEN FLOOR OF LEVEL 06 OF THE |
| | GARAGE AND LEVEL 07 OF THE BUILDING IS SHOWN AS 9'-8". |
| | THESE TWO STRUCTURES ARE DIFFERENT OCCUPANCY TYPES AND |
| | HAVE A FIRE WALL SEPARATING THEM. BECAUSE THE SIXTH |
| | LEVEL OF THE GARAGE IS OPEN ABOVE THERE IS A |
| | POSSIBILITY THAT A CAR FIRE COULD SPREAD TO THE |
| | OPENINGS IN THE ADJACENT RESIDENTIAL BUILDING. SHOW HOW |
| | THIS ISSUE WILL BE RESOLVED. FBC 706.6.1 |
| | |
| | 18) THIS PROJECT IS A THRESHOLD BUILDING. PLEASE UPLOAD |
| | THE THRESHOLD DOCUMENTS FOR THIS PROJECT. THRESHOLD |
| | BUILDING / FL S. S. 553.71(7) "THRESHOLD BUILDING" |
| | MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES |
| | OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 19) 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, LOW |
| | VOLTAGE, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR |
| | ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK |
| | IN COOLERS & FREEZERS, ALL LOW VOLTAGE PERMITS, |
| | GENERATORS & FUEL TANKS, GAS PERMIT, POOLS, WATER |
| | FEATURES, FOUNTAINS, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE |
| | BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS |
| | PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO |
| | COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| | COVERED UNDER THE PRIME OR MASTER PERMIT. |
| | |
| | 20) WHEN RESUBMITTING PAPER PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |