| Plan Review Notes For Permit 18100523 |
| Permit Number |
18100523 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-29 12:19:37 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. SHOW THE BTU LOAD | | | FOR THE EXISTING SYSTEM ON THE GAS RISER. FBC 107.2.1. | | | 2) SHOW THE SIZE OF THE PIPE TO THE EXISTING SYSTEM. | | | FBC 107.2.1. | | | 3) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS | | | METER. THIS SIZE MAY HAVE TO BE INCREASED BASED ON THE | | | LONGEST RUN AND THE TOTAL BTU LOAD ON THE SYSTEM. | | | 4) THE SUBMITTED GAS PLAN SHOWS THE BTU LOAD FOR THE | | | GENERATOR AT 750,000 BTU'S BUT THE GENERAC SPECS SHOW | | | THE BTU LOAD AS 681,000 BTU'S . CLARIFY. | | | 5) PREVIOUS GAS PLAN ON FILE IN CITY RECORDS SHOWS THE | | | DISTANCE TO THE FURTHEST OUTLET AT 202 FEET. THIS | | | DISTANCE SHALL BE USED FOR THE SIZING OF THE GAS LINE | | | TO THE GENERATOR, NOT 50 FEET AS SHOWN. 2017 FBC-FUEL | | | GAS SEC.402.4.1. A MINIMUM SIZE OF 1 INCH PE IS | | | REQUIRED TO THE GENERATOR. TABLE 402.4 (22). | | | 6) THE SIZE OF THE GALVANIZED LINE AT THE OUTLET OF THE | | | GAS METER SHALL BE INCREASED TO 1 1/4 INCH PIPE PER | | | TABLE 402.4 (5). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|