| Date |
Text |
| 2019-12-17 09:59:17 | FOUNDATION ONLY |
| | PLAN REVIEW COMMENTS |
| | |
| | 6TH REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | REMAINING ITEMS TO BE ADDRESSED. |
| | |
| | 1) SECTION 6(2)(E)(II) OF RESOLUTION NO. 185-18 - |
| | CONDITIONS OF APPROVAL REQUIRES A REPLAT PRIOR TO THE |
| | ISSUANCE OF THE FIRST CERTIFICATE OF OCCUPANCY. |
| | |
| | 2) PENDING LOMR. THE ELEVATION OF THE LOWEST FINISHED |
| | FLOOR OF THE PROPOSED RESIDENTIAL STRUCTURE DOES NOT |
| | MEET THE REQUIRED BFE AND 2" FREE-BOARD REQUIREMENTS OF |
| | THE CITY OF WEST PALM BEACH'S FLOOD ORDINANCE FOR NEW |
| | STRUCTURES. NOT COMPLIED. PORTIONS OF THE BUILDING ARE |
| | LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE ELEVATIONS |
| | FOR THE PROJECT ARE IN NGVD 88. AS OF OCTOBER 5TH, 2017 |
| | THE CITY OF WEST PALM BEACH HAS ADOPTED NEW FLOOD |
| | INSURANCE RATE MAPS WHICH USE NAVD 88 AS THE VERTICAL |
| | DATUM. THE CITY ALSO ADOPTED A 2' FREEBOARD WHICH |
| | REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM |
| | OF TWO FEET ABOVE THE BFE. IN ORDER TO AVOID ANY |
| | CONFUSION PLEASE REVISE THE PLANS TO SHOW ONLY THE |
| | CURRENT FLOOD ELEVATION DATA (NAVD 88). ELEVATION |
| | CERTIFICATES WILL BE REQUIRED TO SHOW COMPLIANCE WITH |
| | THE CITY'S FLOOD POLICY. THE CITY REQUIRES THREE |
| | ELEVATION CERTIFICATES. FIRST, A PRECONSTRUCTION ELEV. |
| | CERT. BASED ON THE CONSTRUCTION DRAWING. SECOND, A |
| | CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR |
| | FORMS. THIRD A FINAL ELEV. CERT. BASED ON THE FINISHED |
| | BUILDING. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - |
| | FLOOD PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS |
| | FOR FLOOD HAZARD REDUCTION. |
| | |
| | 3) PENDING. NOT COMPLIED. PROVIDE A COPY OF THE PERMIT |
| | ISSUED BY THE ARMY CORPS OF ENGINEERS/EPA TO FILL IN |
| | THE 9,610 SQFT OF SUBMERGED LAND SHOWN ON THE SITE |
| | PLAN. FBC 107.2.1 |
| | |
| | |