Plan Review Notes
Plan Review Notes For Permit 18100522
Permit Number 18100522
Review Stop P
Sequence Number 4
Notes
Date Text
2019-08-04 04:38:431) A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR EACH
 BUILLDING INCLUDING THE BEACH CLUB BUILDING PER THE
 CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL
 AND THE 2017 FBC-PLUMBING SEC. 608.1. THIS NOTE IS TO
 PLACED ON THE PLUMBING SHEETS.
 2) SHT. C6.00 REFERS TO SHT. C8.00. THIS SHEET IS NOT
 IN THIS SUBMITTAL SUBMIT THIS SHEET SO FURTHER REVIEW
 CAN BE ACCOMPLISHED ON THE WATER SERVICES.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) LABEL ALL THE SANITARY STACKS AND STORM WATER
 LEADERS ON THE FOUNDATION PLANS AND ON THE RISER
 DIAGRAMS SO THEY CORRELATE WITH EACH OTHER AND USE ONE
 SYSTEM OF IDENTIFICATION. NOT ALL OF THE RISERS HAVE
 BEEN LABELED ON THE FOUNDATION PLANS AND WHAT HAS BEEN
 LABELED IS CONFUSING. THERE ARE NUMBERS AND LETTERS
 IDENTIFYING THE SANITARY STACKS AND STORM DRAIN LEADERS
 (E.G.1,2,3; A,B, ETC.) AND ALSO BY AN ALPHA-NUMERIC
 DESIGNATION (SN/ 1, SDS/1, ETC.). THE ALPHA-NUMERIC
 (SN/# & SDS/#) IDENTIFICATION METHOD IS THE PREFERRED
 METHOD FOR THE PLAN REVIEW AND INSPECTION PROCESS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) THE LAYOUT OF THE UNDERGROUND SANITARY AND STORM
 SYSTEM ON SHT. P1.01 DOES NOT CORRELATE WITH THE RISER
 DIAGRAMS AND SOME OF THE PIPE SIZES ON THE FOUNDATION
 PLAN DO NOT MATCH THE RISER DIAGRAM. CLARIFY.
 5) THE FLOOR PLAN LAYOUT FOR THE GARAGE AREA ON SHT.
 P1.01 DOES NOT CORRELATE WITH THE FLOOR PLAN LAYOUT ON
 SHT. PF2.01N. CLARIFY.
 6) SHT. PF2.01S IS LABELED AS SOUTH TOWER PLUMBING AND
 IS ALSO LABELED AS THE NORTH TOWER PLUMBING FOUNDATION.
 PLEASE CORRECT. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SUBMIT A RISER DIAGRAM FOR THE GREASE WASTE AND
 SANITARY SYSTEMS. WPB AMEND. TO FBC SEC. 107.3.5.
 8) SHT. P4.01N REFERS TO AN OIL AND SAND INTERCEPTOR.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.THE
 INTERCEPTOR SHALL COMPLY WITH 2017 FBC - PLUMBING SECS.
 1003.4 - 1003.4.2.1. SHOW THE INTERCEPTOR ON THE RISER
 DIAGRAM.
 9) SHT. PF2.01S - THERE IS A KEYNOTE #27 REFERENCED ON
 THE STORM DRAIN NEAR THE FCC ROOM. THERE IS NO KEYNOTE
 #27 LISTED. CLARIFY.
 10) SHT. PF 2.10S - KEYNOTE #8 CALLS OUT A 10 INCH
 STORM DRAIN BUT THE FOUNDATION PLAN SHOWS A 12 INCH
 STORM DRAIN. THIS LINE IS ALSO SHOWN AS 12 INCH ON THE
 RISER ON SHT. P5.08S. CLARIFY.
 11) SHT. P5.09S SHOWS A 3 INCH FIRE STANDPIPE DRAIN
 CONNECTED TO A 4 INCH STORM DRAIN & SHT. PF 2.01S SHOWS
 IT CONNECTED TO THE ADJACENT 12 INCH STORM DRAIN LINE.
 CLARIFY.
 12) SHT. P5.09S - A 4 INCH PAD IS MISSING ON THE STORM
 RISER DIAGRAM FOR THE GARAGE . THE PAD IS MISSING FROM
 THE 4 INCH STORM DRAIN LINE RUNNING BETWEEN THE PARKING
 SPACES. REFER TO LOCATION OF KEYNOTE #15 ON SHT.
 PF2.01S.
 13) PLACE THE DRAWING NUMBER ON ALL MATCH LINES ON ALL
 PLUMBING SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 14) SHT. A0.101 - "EGRESS STAIRS " BOX - THE NOTE
 STATES" "EACH EGRESS STAIR SHALL HAVE DRAIN(S) AT THE
 LOWEST LANDING." THERE ARE NO DRAINS SHOWN IN EITHER OF
 THE INTERIOR STAIR ENCLOSURES. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  