| 2019-08-04 04:38:43 | 1) A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR EACH |
| | BUILLDING INCLUDING THE BEACH CLUB BUILDING PER THE |
| | CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL |
| | AND THE 2017 FBC-PLUMBING SEC. 608.1. THIS NOTE IS TO |
| | PLACED ON THE PLUMBING SHEETS. |
| | 2) SHT. C6.00 REFERS TO SHT. C8.00. THIS SHEET IS NOT |
| | IN THIS SUBMITTAL SUBMIT THIS SHEET SO FURTHER REVIEW |
| | CAN BE ACCOMPLISHED ON THE WATER SERVICES.WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 3) LABEL ALL THE SANITARY STACKS AND STORM WATER |
| | LEADERS ON THE FOUNDATION PLANS AND ON THE RISER |
| | DIAGRAMS SO THEY CORRELATE WITH EACH OTHER AND USE ONE |
| | SYSTEM OF IDENTIFICATION. NOT ALL OF THE RISERS HAVE |
| | BEEN LABELED ON THE FOUNDATION PLANS AND WHAT HAS BEEN |
| | LABELED IS CONFUSING. THERE ARE NUMBERS AND LETTERS |
| | IDENTIFYING THE SANITARY STACKS AND STORM DRAIN LEADERS |
| | (E.G.1,2,3; A,B, ETC.) AND ALSO BY AN ALPHA-NUMERIC |
| | DESIGNATION (SN/ 1, SDS/1, ETC.). THE ALPHA-NUMERIC |
| | (SN/# & SDS/#) IDENTIFICATION METHOD IS THE PREFERRED |
| | METHOD FOR THE PLAN REVIEW AND INSPECTION PROCESS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 4) THE LAYOUT OF THE UNDERGROUND SANITARY AND STORM |
| | SYSTEM ON SHT. P1.01 DOES NOT CORRELATE WITH THE RISER |
| | DIAGRAMS AND SOME OF THE PIPE SIZES ON THE FOUNDATION |
| | PLAN DO NOT MATCH THE RISER DIAGRAM. CLARIFY. |
| | 5) THE FLOOR PLAN LAYOUT FOR THE GARAGE AREA ON SHT. |
| | P1.01 DOES NOT CORRELATE WITH THE FLOOR PLAN LAYOUT ON |
| | SHT. PF2.01N. CLARIFY. |
| | 6) SHT. PF2.01S IS LABELED AS SOUTH TOWER PLUMBING AND |
| | IS ALSO LABELED AS THE NORTH TOWER PLUMBING FOUNDATION. |
| | PLEASE CORRECT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SUBMIT A RISER DIAGRAM FOR THE GREASE WASTE AND |
| | SANITARY SYSTEMS. WPB AMEND. TO FBC SEC. 107.3.5. |
| | 8) SHT. P4.01N REFERS TO AN OIL AND SAND INTERCEPTOR. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.THE |
| | INTERCEPTOR SHALL COMPLY WITH 2017 FBC - PLUMBING SECS. |
| | 1003.4 - 1003.4.2.1. SHOW THE INTERCEPTOR ON THE RISER |
| | DIAGRAM. |
| | 9) SHT. PF2.01S - THERE IS A KEYNOTE #27 REFERENCED ON |
| | THE STORM DRAIN NEAR THE FCC ROOM. THERE IS NO KEYNOTE |
| | #27 LISTED. CLARIFY. |
| | 10) SHT. PF 2.10S - KEYNOTE #8 CALLS OUT A 10 INCH |
| | STORM DRAIN BUT THE FOUNDATION PLAN SHOWS A 12 INCH |
| | STORM DRAIN. THIS LINE IS ALSO SHOWN AS 12 INCH ON THE |
| | RISER ON SHT. P5.08S. CLARIFY. |
| | 11) SHT. P5.09S SHOWS A 3 INCH FIRE STANDPIPE DRAIN |
| | CONNECTED TO A 4 INCH STORM DRAIN & SHT. PF 2.01S SHOWS |
| | IT CONNECTED TO THE ADJACENT 12 INCH STORM DRAIN LINE. |
| | CLARIFY. |
| | 12) SHT. P5.09S - A 4 INCH PAD IS MISSING ON THE STORM |
| | RISER DIAGRAM FOR THE GARAGE . THE PAD IS MISSING FROM |
| | THE 4 INCH STORM DRAIN LINE RUNNING BETWEEN THE PARKING |
| | SPACES. REFER TO LOCATION OF KEYNOTE #15 ON SHT. |
| | PF2.01S. |
| | 13) PLACE THE DRAWING NUMBER ON ALL MATCH LINES ON ALL |
| | PLUMBING SHEETS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 14) SHT. A0.101 - "EGRESS STAIRS " BOX - THE NOTE |
| | STATES" "EACH EGRESS STAIR SHALL HAVE DRAIN(S) AT THE |
| | LOWEST LANDING." THERE ARE NO DRAINS SHOWN IN EITHER OF |
| | THE INTERIOR STAIR ENCLOSURES. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |