Plan Review Notes
Plan Review Notes For Permit 18100522
Permit Number 18100522
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-08 13:10:54PLUMBING 2ND REVIEW**DENIED**
  
 1) 2ND REQUEST: PROVIDE A SANITARY AND STORM ISOMETRIC
 DRAWING FOR THE S. FBC 107.3.5**WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 2) PROVIDE INSTALLATION MANUALS FOR THE GREASE
 INTERCEPTORS. FBC 107.2.1
  
 3) ALL PLUMBING SHEET SHOW BOTH DRINKING FOUNTAINS
 DISCHARGING INTO THE BATHROOM GROUP WET VENT. DRINKING
 FOUNTAINS SHALL DISCHARGE DOWN STREAM OF THE BATHRROM
 GROUP. FBC 912.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR