| Plan Review Notes For Permit 18100482 |
| Permit Number |
18100482 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-11-02 12:49:20 | ****CORRECTIONS**** | | | COURTESY REVIEW AFTER NEW INFORMATION FROM GC | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | | | | 1. FBC 107, CLARIFY SCOPE. IT APPEARS THAT A PORTION OF | | | THE ROOF (<25%) NEEDS TO BE REMOVED AND REPLACED, AND | | | THE REMAINDER RECOVERED. APPLICATION PROPOSES A | | | RECOVER. DRAINS AND SCUPPERS ARE SHOWN; IT IS NOT CLEAR | | | IF THESE ARE PROPOSED OR EXISTING. DRAINAGE | | | CALCULATIONS MAY BE REQUIRED. | | | | | | 2ND REVIEW - PER CONTRACTOR, THE PORTION WITH EXCESS | | | MOISTURE IS TO BE REMOVED AND REPLACED, SCUPPERS AND | | | DRAINS EXISTING. IS THIS CORRECT? | | | | | | PROVIDE AN ASSEMBLY FOR THE PORTION OF ROOF REQUIRING A | | | REROOF. | | | | | | IT IS NOT CLEAR WHY ROOFING CONTRACTOR IS PROPOSING A | | | RECOVER AND ENGINEER PROVIDES CALCULATIONS FOR RECOVER | | | WHEN ENGINEER'S MOISTURE TEST SHOWS EXCESSIVE MOISTURE; | | | PLEASE CLARIFY. | | | | | | | | | | | | | | | |
|