2018-11-02 12:49:20****CORRECTIONS****
 COURTESY REVIEW AFTER NEW INFORMATION FROM GC
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 1. FBC 107, CLARIFY SCOPE. IT APPEARS THAT A PORTION OF
 THE ROOF (<25%) NEEDS TO BE REMOVED AND REPLACED, AND
 THE REMAINDER RECOVERED. APPLICATION PROPOSES A
 RECOVER. DRAINS AND SCUPPERS ARE SHOWN; IT IS NOT CLEAR
 IF THESE ARE PROPOSED OR EXISTING. DRAINAGE
 CALCULATIONS MAY BE REQUIRED.
  
 2ND REVIEW - PER CONTRACTOR, THE PORTION WITH EXCESS
 MOISTURE IS TO BE REMOVED AND REPLACED, SCUPPERS AND
 DRAINS EXISTING. IS THIS CORRECT?
  
 PROVIDE AN ASSEMBLY FOR THE PORTION OF ROOF REQUIRING A
 REROOF.
  
 IT IS NOT CLEAR WHY ROOFING CONTRACTOR IS PROPOSING A
 RECOVER AND ENGINEER PROVIDES CALCULATIONS FOR RECOVER
 WHEN ENGINEER'S MOISTURE TEST SHOWS EXCESSIVE MOISTURE;
 PLEASE CLARIFY.
  
  
  
  
  