| 2018-10-15 08:14:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, CLARIFY SCOPE. IT APPEARS THAT A PORTION OF | | | THE ROOF (<25%) NEEDS TO BE REMOVED AND REPLACED, AND | | | THE REMAINDER RECOVERED. APPLICATION PROPOSES A | | | RECOVER. DRAINS AND SCUPPERS ARE SHOWN; IT IS NOT CLEAR | | | IF THESE ARE PROPOSED OR EXISTING. DRAINAGE | | | CALCULATIONS MAY BE REQUIRED. | | | | | | | | | | | | |
|