| Notes |
| Date |
Text |
| 2018-12-18 15:59:30 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SHEET LS1-01: A) NUMBER OF PEOPLE SHOWN ON OCCUPANCY | | | CALCULATION ON THE RIGHT HAND SIDE OF DRAWING DOESN'T | | | MATCH NUMBER OF PEOPLE SHOWN ON FLOOR PLAN. CHECK | | | ASSEMBLY OCCUPANTS AND REVISE. | | | B)CODE SECTION REFERENCES CITED ON THE CODE ANALYSIS | | | LEGEND AND EGRESS TRAVEL CALCULATIONS DON'T CORRESPOND | | | TO THE CURRENT FBC 6TH EDITION (2017). REVISE AS | | | REQUIRED. | | | C) FLOOR PLAN SHOWS ONE PARTITION WALL IN THE LEFT HAND | | | SIDE CORRIDOR OF FLOOR PLAN AND ANOTHER PARTITION WALL | | | LOCATED IN THE UPPER LEFT CORNER CORRIDOR (SEE MARK UPS | | | ON FLOOR PLAN). IT IS NOT CLEAR IF THESE ARE TRUE | | | PARTITIONS. THERE IS NOT ACCESS TO THE OFFICES LOCATED | | | IN THE UPPER LEFT CORNER. CLARIFY/REVISE. |
|