Plan Review Notes
Plan Review Notes For Permit 18100445
Permit Number 18100445
Review Stop B
Sequence Number 2
Notes
Date Text
2018-12-18 15:59:30BUILDING REVIEW APPROVED WITH PROVISO:
 1- SHEET LS1-01: A) NUMBER OF PEOPLE SHOWN ON OCCUPANCY
 CALCULATION ON THE RIGHT HAND SIDE OF DRAWING DOESN'T
 MATCH NUMBER OF PEOPLE SHOWN ON FLOOR PLAN. CHECK
 ASSEMBLY OCCUPANTS AND REVISE.
 B)CODE SECTION REFERENCES CITED ON THE CODE ANALYSIS
 LEGEND AND EGRESS TRAVEL CALCULATIONS DON'T CORRESPOND
 TO THE CURRENT FBC 6TH EDITION (2017). REVISE AS
 REQUIRED.
 C) FLOOR PLAN SHOWS ONE PARTITION WALL IN THE LEFT HAND
 SIDE CORRIDOR OF FLOOR PLAN AND ANOTHER PARTITION WALL
 LOCATED IN THE UPPER LEFT CORNER CORRIDOR (SEE MARK UPS
 ON FLOOR PLAN). IT IS NOT CLEAR IF THESE ARE TRUE
 PARTITIONS. THERE IS NOT ACCESS TO THE OFFICES LOCATED
 IN THE UPPER LEFT CORNER. CLARIFY/REVISE.