| 2018-12-04 17:21:57 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 1- SHEET LS1-01: |
| | A) NUMBER OF PEOPLE SHOWN ON OCCUPANCY CALCULATION ON |
| | THE RIGHT HAND SIDE OF DRAWING DOESN'T MATCH NUMBER OF |
| | PEOPLE SHOWN ON FLOOR PLAN. CHECK ASSEMBLY OCCUPANTS |
| | AND REVISE AS REQUIRED. TABLE 1004.1.2 FBC. |
| | |
| | B)CODE SECTION REFERENCES CITED ON THE CODE ANALYSIS |
| | LEGEND AND EGRESS TRAVEL CALCULATIONS DON'T CORRESPOND |
| | TO THE CURRENT FBC 6TH EDITION (2017). REVISE AS |
| | REQUIRED TO AVOID CONFLICTS. SEC. 107.2.1 CITY |
| | AMENDMENTS AND CHAPTER 553 F.S. |
| | |
| | C) FLOOR PLAN SHOWS ONE PARTITION WALL IN THE LEFT HAND |
| | SIDE CORRIDOR OF FLOOR PLAN AND ANOTHER PARTITION WALL |
| | LOCATED IN THE UPPER LEFT CORNER CORRIDOR (SEE MARK UPS |
| | ON FLOOR PLAN). IT IS NOT CLEAR IF THESE ARE TRUE |
| | PARTITIONS. THERE IS NOT ACCESS TO THE OFFICES LOCATED |
| | IN THE UPPER LEFT CORNER. CLARIFY/REVISE AS REQUIRED. |
| | NOTE: REVISE ALL DRAWINGS ACCORDINGLY. ALL OF THEM SHOW |
| | THESE PARTITIONS SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | |