| 2019-04-17 14:23:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PLEASE NOTE THAT IN ACCORDANCE WITH THE PROVISIONS |
| | OF FBC PL 403.3.3 (WHICH ADDRESSES LOCATION OF TOILET |
| | FACILITIES WITH A PATH OF TRAVEL TO SUCH FACILITIES |
| | SHALL NOT EXCEED A DISTANCE OF 500 FEET) AND BASED UPON |
| | THE SUPPORTING DOCUMENTS PROVIDED IN THE THE |
| | ARCHITECT'S RESPONSE LETTER DATED 1/24/19, NEW TOILET |
| | FACILITIES ARE NOT REQUIRED IN THE NEW STRUCTURE. |
| | HOWEVER, PER TABLE 403.1 AND NOTING THAT THE OCCUPANCY |
| | LOAD OF THE NEW STRUCTURE IS GREATER THAN 15, A |
| | DRINKING FOUNTAIN (CONFORMING TO THE REQUIREMENTS OF |
| | FBC PL 410 AND FBC ACC 602) AND A SERVICE SINK IS |
| | REQUIRED. |
| | 2. PLEASE REFER TO C-2 PAVING AND GRADING PLAN AND |
| | A-3.0 EXTERIOR ELEVATIONS. PER WPB FBC 107.2.1 PROVIDE |
| | THE FOLLOWING. |
| | A. RECONCILE DOWNSPOUT LOCATIONS BETWEEN THE TWO PLANS. |
| | B. PROVIDE STORM DRAIN CALCULATIONS AND SIZING OF |
| | GUTTERS AND DOWNSPOUTS. |
| | 3. PER WPB FBC 107.2.1, REMOVE NON-APPLICABLE ITEMS |
| | FROM THE FOLLOWING DRAWINGS; A1.1, P1.0 AND P2.0. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |