| 2019-04-26 15:46:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. LOAD CALCULATION SHOWS A DEMAND LOAD FOR KITCHEN |
| | EQUIPMENT AT 50%. I SEE NO KITCHEN EQUIPMENT THAT WOULD |
| | QUALIFY FOR A DEMAND LOAD REDUCTION. ALSO, A REDUCTION |
| | OF 50% FOR KITCHEN EQUIPMENT DOES NOT EXIST. PROVIDE |
| | CORRECTION. NEC 220.56 (THE LOAD CALCULATION IS STILL |
| | INCORRECT. THE DEMAD FACTOR APPLIED FOR RECEPTACLE |
| | LOADS IS NOT PERMITTED FOR ALL OF THESE LOADS. SOME OF |
| | THESE ARE NOT STANDARD RECEPTACLES FIGURED AT 180 VA |
| | PER STRAP. THE MOTOR LOADS SHOULD BE CALCULATED PER NEC |
| | 220.14(C). PROVIDE CORRECTION.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. PROVIDE CLARIFICATION FOR FIRE SPRINKLER FEED, WILL |
| | THERE BE A FIRE SPRINKLER PUMP, OR IS THE WATER |
| | PRESSURE FROM CITY ACCEPTABLE AND A FIRE PUMP WILL NOT |
| | BE REQUIRED? IF FIRE PUMP REQUIRED, INCLUDE ELECTRICAL |
| | DETAILS. WPB FBC 107.2.1 (QUESTION NOT ANSWERED. AS THE |
| | REQUIREMENTS FOR A FIRE PUMP WOULD CHANGE THE DESIGN OF |
| | THE ELECTRICAL SERVICE, THIS INFORMATION IS REQUIRED.) |
| | 7. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |