| 2018-11-26 09:41:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18100354 |
| | 11/26/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.0: RECIRCULATION OF AIR FROM THE GARAGE |
| | INTO THE LOUNGE AREA AND THE TOILET ROOM IS PROHIBITED |
| | PER TABLE 403.3.1.1 FOOTNOTE B FBC M. |
| | |
| | 2) M2.0: SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE CO AND NO2 SENSORS |
| | AND THE CONTROL PANEL- SECTION 404.1 FBC M. |
| | |
| | 3) M2.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION |
| | 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| | SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| | SUPPLY AIR. |
| | |
| | 4) M1.0: PROVIDE THE MINIMUM VENTILATION RATE FOR THE |
| | LOUNGE ROOM- TABLE 403.3.1.1 FBC M. |
| | |
| | 5) M2.0: PLEASE IDENTIFY ALL APPLIANCES IN THE KITCHEN |
| | AND PROVIDE A EQUIPMENT LIST. SUBMIT MANUFACTURER |
| | SPECIFICATIONS FOR ALL COOKING APPLIANCES AND EXHAUST |
| | HOODS ( IF APPLICABLE). PLEASE NOTE THAT SEPARATE |
| | PERMITS ARE REQUIRED FOR COMMERCIAL KITCHEN EXHAUST AND |
| | FIRE SUPPRESSION SYSTEMS- SECTION 107.1 WPB. |
| | |
| | 6) M2.0: PROVIDE CONSTRUCTION DETAILS FOR THE CONDENSER |
| | PADS, AND INDICATE THE TYPE AND SIZE OF ANCHOR BOLT FOR |
| | ATTACHING THE UNITS TO THE PADS- SECTION 301.15 FBC M. |
| | |
| | 7) M1.0: THE MIAMI-DADE NOA #12-0830.07 FOR THE LOUVERS |
| | IS EXPIRED, AND HAS BEEN REPLACED WITH #16-0201.02. |
| | PLEASE CORRECT THE NOTES ON THE PLAN AND SUBMIT THE |
| | NOA. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |