| 2018-10-16 16:15:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 110 & CS 1 - THERE IS A "YES" INDICATED |
| | WITHIN THE LIFE SAFETY SUMMARY & BLDG CODE TABLE ON THE |
| | FIRE SPRINKLER LINE. |
| | |
| | PLEASE CONFIRM THAT A FIRE SPRINKLER SYSTEM IS PROPOSED |
| | FOR THIS STRUCTURE. |
| | |
| | THERE ARE NO FIRE SPRINKLER FAC 61G REQUIRED DOCUMENTS |
| | FOR THIS SPRINKLER SYSTEM. |
| | |
| | |
| | FIRE SPRINKLERS |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTS WITH THIS MASTER |
| | PERMIT, EITHER IN NARRATIVE FORM OF PLAN DRAWINGS, |
| | SIGNED AND SEALED BY THE EOR. |
| | |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF A MONITORED FIRE |
| | SPRINKLER SYSTEM. THE CODE REQUIRES THAT THE FIRE |
| | SPRINKLER SYSTEM BE MONITORED. |
| | |
| | |
| | PER NFPA 101, CHAPTER 9, FIRE PROTECTION SYSTEMS |
| | |
| | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 9.6.1* GENERAL. |
| | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| | SYSTEM OR NEW FIRE ALARMS SYSTEM IS REQUIRED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 2017 FLORIDA BUILDING CODE: |
| | |
| | 901.6 SUPERVISORY SERVICE. |
| | WHERE REQUIRED, FIRE PROTECTION SYSTEMS SHALL BE |
| | MONITORED BY AN APPROVED SUPERVISING STATION IN |
| | ACCORDANCE WITH NFPA 72. |
| | 901.6.1 AUTOMATIC SPRINKLER SYSTEMS. |
| | |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE MONITORED BY AN |
| | APPROVED SUPERVISING STATION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| | AND COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 3) SHEET CS 1 - A LOW HAZARD STORAGE OCCUPANCY IS |
| | INDICATED. |
| | |
| | |
| | PER NFPA 101 CHAPTER 42, STORAGE OCCUPANCIES. |
| | |
| | 42.1.5 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 42.1.5.1 CONTENTS OF STORAGE OCCUPANCIES SHALL BE |
| | CLASSIFIED AS |
| | LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD IN |
| | ACCORDANCE WITH |
| | SECTION 6.2, DEPENDING ON THE QUANTITY AND CHARACTER OF |
| | THE |
| | MATERIALS STORED, THEIR PACKAGING, AND OTHER FACTORS. |
| | |
| | 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL |
| | BE |
| | CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO |
| | SELFPROPAGATING |
| | FIRE THEREIN CAN OCCUR. |
| | |
| | PER NFPA 42, STORAGE OCCUPANCIES |
| | |
| | 42.8.1.5 CLASSIFICATION OF HAZARD OF CONTENTS. PARKING |
| | STRUCTURES USED ONLY FOR THE STORAGE OF VEHICLES SHALL |
| | BE CLASSIFIED |
| | AS ORDINARY HAZARD IN ACCORDANCE WITH SECTION 6.2. |
| | |
| | |
| | THE PROPOSED BUILDING USE OCCUPANCY CLASSIFICATION |
| | APPEARS TO ORDINARY HAZARD |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 4) SHEET CS 1 - IT ALSO STATES THIS IS A 1 STORY |
| | VEHICLE BUILDING. |
| | |
| | PER CHAPTER 42 - STORAGE OCCUPANCIES. |
| | |
| | 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES. |
| | 42.8.1 GENERAL REQUIREMENTS. |
| | 42.8.1.1* APPLICATION. THE PROVISIONS OF 42.8.1 THROUGH |
| | 42.8.5.4 |
| | SHALL APPLY TO PARKING STRUCTURES OF THE CLOSED OR OPEN |
| | TYPE, ABOVE |
| | OR BELOW GRADE PLANE, BUT SHALL NOT APPLY TO ASSISTED |
| | MECHANICALTYPE |
| | OR AUTOMATED-TYPE PARKING FACILITIES THAT ARE NOT |
| | OCCUPIED BY |
| | CUSTOMERS. THE REQUIREMENTS OF SECTIONS 42.1 THROUGH |
| | 42.7 SHALL |
| | NOT APPLY. |
| | |
| | PER NFPA 101, CHAPTER 2 DEFINITIONS |
| | |
| | 3.3.272.7* PARKING STRUCTURE. A BUILDING, STRUCTURE, OR |
| | PORTION |
| | THEREOF USED FOR THE PARKING, STORAGE, OR BOTH, OF |
| | MOTOR VEHICLES. |
| | [88A, 2015] |
| | |
| | PER NFPA 88A, STANDARD FOR PARKING STRUCTURES 2015 |
| | EDITION |
| | |
| | 6.4 FIRE SPRINKLER SYSTEMS. |
| | 6.4.1 AUTOMATIC SPRINKLER SYSTEMS SHALL CONFORM TO NFPA |
| | 13. |
| | 6.4.2 AUTOMATIC SPRINKLER SYSTEMS SHALL BE INSTALLED IN |
| | PORTIONS |
| | OF ENCLOSED PARKING STRUCTURES, THE CEILINGS OF WHICH |
| | ARE |
| | LESS THAN 600 MM (24 IN.) ABOVE GRADE, REGARDLESS OF |
| | TYPE OF |
| | CONSTRUCTION, AND IN ENCLOSED PARKING STRUCTURES OF |
| | TYPE III OR |
| | TYPE IV CONSTRUCTION OVER 15 M (50 FT) IN HEIGHT. |
| | 6.4.3 AUTOMATIC SPRINKLER SYSTEMS SHALL BE INSTALLED IN |
| | ENCLOSED |
| | PARKING STRUCTURES LOCATED AT OR ABOVE GRADE, OR WITHIN |
| | OR IMMEDIATELY BELOW A BUILDING USED FOR ANOTHER |
| | OCCUPANCY. |
| | EXCEPTION: ENCLOSED PARKING STRUCTURES DESCRIBED ABOVE, |
| | HAVING AN |
| | APPROVED, SUPERVISED, AUTOMATIC FIRE DETECTION AND |
| | ALARM SYSTEM INSTALLED |
| | THROUGHOUT THE PARKING AREA IN ACCORDANCE WITH NFPA 72 |
| | AND |
| | A MECHANICAL VENTILATION SYSTEM IN ACCORDANCE WITH |
| | 5.3.2. |
| | 6.4.4 AUTOMATIC SPRINKLER SYSTEMS SHALL NOT BE REQUIRED |
| | IN |
| | OPEN PARKING STRUCTURES. |
| | |
| | |
| | BASED ON THE PROVIDED INFORMATION THIS IS AN ENCLOSED |
| | PARKING STRUCTURE |
| | |
| | PLEASE REVIEW, CONFIRM AND CORRECT AND PROVIDE REQUIRED |
| | 61G DOCUMENTS NOTED IN # 1 ABOVE. |
| | . |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |