| Date |
Text |
| 2018-11-08 15:50:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION SHOWS A DEMAND LOAD FOR KITCHEN |
| | EQUIPMENT AT 50%. I SEE NO KITCHEN EQUIPMENT THAT WOULD |
| | QUALIFY FOR A DEMAND LOAD REDUCTION. ALSO, A REDUCTION |
| | OF 50% FOR KITCHEN EQUIPMENT DOES NOT EXIST. PROVIDE |
| | CORRECTION. NEC 220.56 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 3. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS |
| | IN GARAGE, INCLUDING CORD REELS. NEC 511.12 |
| | 4. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS |
| | WITHIN 6 FEET OF A SINK. NEC 210.8 |
| | 5. GENERAL NOTE 1 ON SHEET E4.0 STATES THAT ALL |
| | CONDUITS SHALL BE RUN IN CAVITY OF PURLIN. THIS IS A |
| | CODE VIOLATION. PROVIDE CORRECTION. NEC 300.4(E) |
| | 6. PROVIDE CLARIFICATION FOR FIRE SPRINKLER FEED, WILL |
| | THERE BE A FIRE SPRINKLER PUMP, OR IS THE WATER |
| | PRESSURE FROM CITY ACCEPTABLE AND A FIRE PUMP WILL NOT |
| | BE REQUIRED? IF FIRE PUMP REQUIRED, INCLUDE ELECTRICAL |
| | DETAILS. WPB FBC 107.2.1 |
| | 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |