| Plan Review Notes For Permit 18100350 |
| Permit Number |
18100350 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-14 15:06:10 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1.SHT.A2-04-A IT APPEARS THAT YOU ELIMINATED TWO OVER | | | FLOW DRAIN AND REPLACED THEM WITH EMERGENCY SCUPPER | | | DRAIN THESE PAGE ONLY SHOWS ONE PLEASE SHOE THE | | | LOCATION OF THE 2ND EMERGENCY SCUPPER AND PROVIDE | | | DETAIL SHOW THE DOMINATIONS OF SCUPPER. PER FBC PL | | | 1108.1 , 1108.3 | | | | | | 2. THE WATER FOUNTAIN THAT WAS ELIMINATED IS A REQUIRED | | | FIXTURE FOR THE A5 OCCUPANCY IT SHALL REMAIN THE | | | SUBSTITUTION IS ONLY FOR A2 OCCUPANCY TYPES FBC PL | | | TABLE 403.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|