| Plan Review Notes For Permit 18100338 |
| Permit Number |
18100338 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-05 09:04:51 | PROVISO: | | | 1. THE LAVATORY SINKS IN THE BATHROOM SHALL SUPPLY | | | TEMPERED WATER ONLY THROUGH A TEMPERATURE LIMITING | | | DEVICE THAT COMPLIES WITH ASSE 1070 OR CSA B125.3. THE | | | MIXING VALVE ON THE WHOLE HOT WATER SYSTEM DOES NOT | | | COMPLY WITH ASSE 1070 OR CSA B125.3 SHALL COMPLY WITH | | | FBC PL 416.5 | | | 2. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED FOR THE | | | BAR SINK IT IS SHOWN ON THE WATER HEATER DETAIL ON | | | SHT.P0.1 BUT IS NOT SHOWN ON THE FLOOR PLAN OR THE | | | WATER ISOMETRIC. SHALL COMPLY WITH FBC PL 607.2 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|