| Date |
Text |
| 2018-11-01 09:03:30 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE ENLARGED DETAIL FLOOR PLAN SHOWING |
| | THE CLEAR FLOOR SPACE FOR THE TOILETS AND LAVATORIES |
| | WITH DIMENSIONS. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 2. PER FBC ACC CH6 PLEASE PROVIDE DETAILS SHOWING |
| | HEIGHT REQUIREMENTS FOR ACCESSIBILITY FOR THE |
| | FOLLOWING. |
| | A) FBC ACC 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE |
| | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | B) FBC ACC 604.7 DISPENSERS. TOILET PAPER DISPENSERS |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. |
| | C) FBC ACC 604.4 SEATS. THE SEAT HEIGHT OF A WATER |
| | CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES |
| | MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF |
| | THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A |
| | LIFTED POSITION. |
| | D) FBC ACC 604.2 LOCATION. THE WATER CLOSET SHALL BE |
| | POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO |
| | ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| | WALL OR PARTITION, |
| | E) FBC ACC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR |
| | SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES |
| | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES |
| | MINIMUM FROM THE REAR WALL. |
| | F) FBC ACC 604.5.2 REAR WALL. THE REAR WALL GRAB BAR |
| | SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE |
| | CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE |
| | SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. |
| | G) FBC ACC 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL |
| | BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| | H) FBC ACC 603.3 MIRRORS. MIRRORS LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED |
| | ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| | THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. PER FBC PL 1108.1 WHERE ROOF DRAINS ARE REQUIRED, |
| | SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS |
| | SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION |
| | EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL |
| | BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR |
| | ANY REASON. WHERE PRIMARY AND SECONDARY ROOF DRAINS ARE |
| | MANUFACTURED AS A SINGLE ASSEMBLY, THE INLET AND OUTLET |
| | FOR EACH DRAIN SHALL BE INDEPENDENT. AND SHALL COMPLY |
| | WITH FBC PL 1108.2 AND 1108.3 |
| | |
| | 4. ARE THE ROOF SCUPPERS ON THE WEST SIDE OF THE |
| | EXISTING ROOF AREA 5 DUMPING INTO A DOWN SPOUT OR ONTO |
| | THE AREA 2 + 3 ROOFS PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 5. PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING. PER |
| | WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 6. HOW WILL THE FLOOR DRAIN IN THE DUMPSTER ENCLOSURE |
| | BE PROTECTED FROM RECEIVING STORM WATER DISCHARGE. |
| | STORM WATER SHALL NOT DISCHARGE INTO THE SANITARY |
| | SEWER. PER WPB CODE OF ORDINANCE SEC. 90-126.(5) |
| | |
| | 7. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS AND |
| | INSTALLATION GUIDE FROM SCHIER FOR THE GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. UNDER THE KITCHEN PLUMBING SCHEDULE IT LIST $ OF THE |
| | K7 HAND SINKS THE PLAN ONLY SHOWS ONE PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. ONLY THE LAVATORIES IN THE BATHROOMS SHALL BE |
| | SUPPLIED WITH TEMPERED WATER ONLY ALL OTHER PLUMBING |
| | FIXTURES THAT ARE USED FOR CULINARY PURPOSES, |
| | CLEANSING, LAUNDRY OR BUILDING MAINTENANCE PURPOSES |
| | SHALL HAVE HOT WATER. PER FBC PL 607.1, 416.5, 202 |
| | |
| | 10. PLEASE PLACE NOTE ON PLAN SEPARATE PERMITS ARE |
| | REQUIRED FOR THE GREASE INTERCEPTOR, BACKFLOW DEVICE AT |
| | THE METER AND THE GAS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |