2018-11-01 09:03:301ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE ENLARGED DETAIL FLOOR PLAN SHOWING
 THE CLEAR FLOOR SPACE FOR THE TOILETS AND LAVATORIES
 WITH DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
 2. PER FBC ACC CH6 PLEASE PROVIDE DETAILS SHOWING
 HEIGHT REQUIREMENTS FOR ACCESSIBILITY FOR THE
 FOLLOWING.
 A) FBC ACC 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 B) FBC ACC 604.7 DISPENSERS. TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
 C) FBC ACC 604.4 SEATS. THE SEAT HEIGHT OF A WATER
 CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
 LIFTED POSITION.
 D) FBC ACC 604.2 LOCATION. THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION,
 E) FBC ACC 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR
 SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL.
 F) FBC ACC 604.5.2 REAR WALL. THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE.
 G) FBC ACC 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 H) FBC ACC 603.3 MIRRORS. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3. PER FBC PL 1108.1 WHERE ROOF DRAINS ARE REQUIRED,
 SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS
 SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION
 EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL
 BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR
 ANY REASON. WHERE PRIMARY AND SECONDARY ROOF DRAINS ARE
 MANUFACTURED AS A SINGLE ASSEMBLY, THE INLET AND OUTLET
 FOR EACH DRAIN SHALL BE INDEPENDENT. AND SHALL COMPLY
 WITH FBC PL 1108.2 AND 1108.3
  
 4. ARE THE ROOF SCUPPERS ON THE WEST SIDE OF THE
 EXISTING ROOF AREA 5 DUMPING INTO A DOWN SPOUT OR ONTO
 THE AREA 2 + 3 ROOFS PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. HOW WILL THE FLOOR DRAIN IN THE DUMPSTER ENCLOSURE
 BE PROTECTED FROM RECEIVING STORM WATER DISCHARGE.
 STORM WATER SHALL NOT DISCHARGE INTO THE SANITARY
 SEWER. PER WPB CODE OF ORDINANCE SEC. 90-126.(5)
  
 7. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS AND
 INSTALLATION GUIDE FROM SCHIER FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 8. UNDER THE KITCHEN PLUMBING SCHEDULE IT LIST $ OF THE
 K7 HAND SINKS THE PLAN ONLY SHOWS ONE PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 9. ONLY THE LAVATORIES IN THE BATHROOMS SHALL BE
 SUPPLIED WITH TEMPERED WATER ONLY ALL OTHER PLUMBING
 FIXTURES THAT ARE USED FOR CULINARY PURPOSES,
 CLEANSING, LAUNDRY OR BUILDING MAINTENANCE PURPOSES
 SHALL HAVE HOT WATER. PER FBC PL 607.1, 416.5, 202
  
 10. PLEASE PLACE NOTE ON PLAN SEPARATE PERMITS ARE
 REQUIRED FOR THE GREASE INTERCEPTOR, BACKFLOW DEVICE AT
 THE METER AND THE GAS. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  