| 2018-10-12 14:01:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) SHEET A 003R - THERE IS AN INCORRECT EDITION OF THE |
| | FLORIDA FIRE PREVENTION CODE |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 101R - THERE IS AN INDICATION OF DOOR 3 |
| | SWINGING OUT INTO THE EXIT ACCESS CORRIDOR. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PER CHAPTER 12, NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.3.8 MINIMUM CORRIDOR WIDTH. THE WIDTH OF ANY EXIT |
| | ACCESS CORRIDOR SERVING 50 OR MORE PERSONS SHALL BE NOT |
| | LESS THAN |
| | 44 IN. (1120 MM). |
| | |
| | |
| | PLEASE FIELD VARIFY AND ENSURE THAT THE WIDTH OF THE |
| | REMANING CORRIDOR WHEN THE DOOR IS OPEN IS NOT LESS |
| | THAN 22". |
| | |
| | |
| | |
| | |
| | 3) SHEET FS 1.1 - THE PTOPOSED FIRE SPRINKLER SYSTEM |
| | SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS BY A |
| | CERTIFIED FIRE SPRINKLER CONTRACTOR. |
| | |
| | |