Plan Review Notes
Plan Review Notes For Permit 18100338
Permit Number 18100338
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-18 14:56:34****CORRECTIONS****
 W.P.B. PERMIT: 18100338
 REVIEWED: OCTOBER 18, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC A307.2] AND [FBC 1003.3]PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH
 THE HAND WASH SINK IS PROTRUDING INTO CIRCULATION PATH
 AND MAY ALSO REDUCE THE EGRESS TO LESS THAN THE
 REQUIRED 44? MINIMUM. PLEASE REVIEW AND ADJUST LOCATION
 AS NEEDED.
  
 2. [FBC 307.4] VERTICAL CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 WHAT IS HAPPENING AT THE REAR DOOR WHERE THE EXISTING
 STAIRS ARE? I SEE AN ICE MAKER, BUT ITS NOT CLEAR WHERE
 80? IS AND WHAT IF THIS EQUIPMENT IS MOVED?
  
 3. [FBC 1017.2]ADD MAXIMUM TRAVEL DISTANCE TO SHEET
 A-103R.
 INCLUDE EXIT DISCHARGE DISTANCE TO PUBLIC RIGHT OF WAY
 FROM REAR EXITS AND INCLUDE OUTDOOR AREA IN LIFE SAFETY
 PLAN PER FBC 1004.5.
 REMOVE OLD LABEL THAT SAY EXISTING TAYLOR SHOP.
  
 4. [FBC 107.2.5]SHOW LOCATION OF STEEL POSTS FROM
 S-101R ON THE FLOOR PLAN. HOW WILL THE PROPOSED POCKET
 DOOR FUNCTION WITH THE POST IN THE WALL CAVITY?
 ADD TYPICAL DETAIL OF EXTERIOR WALL TO SHOW INSULATION,
 FURRING AND INTERIOR WALL MATERIAL.
  
 5. [FBC A404.2.4.1(C)]DOOR LABELED 6 AT THE REAR
 EGRESS. PROVIDE 12? SIDE CLEARANCE AT DOOR WITH FRONT
 APPROACH PUSH SIDE WITH CLOSER AND LATCH.
  
 6. [FBC A902.1]SHEET A-101R SHOWS ADA SECTION AT BAR.
 PROVIDE DETAIL OF HOW IT COMPLYS WITH ADA REQUIREMENTS.
 SHOW DETAIL OF HOW THE BAR IS CONSTRUCTED AND CONNECTED
 TO FLOOR.
 ALSO, SHOW DETAIL OF GLASS WALL AT ENTRY.
  
 7. [FBC A604 AND A606.1]INTERIOR ELEVATIONS OF ADA
 RESTROOMS TO COMPLY WITH A604-A606.
  
 8. [FBC A604.6]SHOW FLUSHING CONTROL TO BE ON THE OPEN
 SIDE OF THE WATER CLOSET.
  
 9. [FBC A604.5]ADD NOTE TO SUPPLY BACKING SUPPORT FOR
 RESTROOM GRAB BARS.
  
 10. [FBC A604.5.1] THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
 SHOW LENGTH OF BACK GRAB BARS IN RESTROOMS
  
 11. [FBC A604.5.2] THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 SHOW LENGTH OF SIDE GRAB BARS IN RESTROOMS
  
 12. [FBC 1511.1.1]WHAT PERCENTAGE OF ROOF IS BEING
 REPLACED? IF IT EXCEEDS 25% THAN THE WHOLE ROOF SHOULD
 BE REPLACED TO MEET CURRENT CODES.
  
 13. [FBC 1510.10]MECHANICAL UNITS.
 HOW ARE NEW RTU?S BEING SUPPORTED? PLEASE PROVIDE
 DETAILS OF HOW THESE UNITS ARE SUPPORTED ON THE ROOF.
  
 14. [FBC 1203.3]UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES.
 PROVIDE CUT SHEET FOR ICYNENE(ICC-ES REPORT OR EQUAL)
 WITH THE TYPE SELECTED TO ESTABLISH THICKNESS NEEDED TO
 MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX.
 ALSO, ADJUST SHEET S-102R DETAIL SHOWS R-21 AT ROOF,
 BUT THE ENERGY CALCULATIONS CALL FOR R23.1.
  
 15. [FBC 1609.1.1]DETERMINATION OF WIND LOADS FOR
 COMPONANTS AND CLADDING.
 PROVIDE WIND LOAD DESIGN DATA FOR COMPONANTS AND
 CLADDING.
 METHOD OF DESIGN = (ASCE 7-10?)
 RISK CATEGORY = ___(II?)
 EXPOSURE CATEGORY = ___(B,C OR D?)
 BUILDING CLASSIFICATION = __________(ENCLOSED?)
 MEAN BLDG. HGT. = ___FT. ___IN.
 WIND SPEED V ULT = _____(170?)
 WIND SPEED V ASD = _____(132?)
 DESIGN PRESSURE FOR EACH OPENING = +___ & -___ ZONE OF
 OPENING = (4 OR 5)
  
 16. THE FOLLOWING SUBMITTALS WILL BE DEFERRED AS STATED
 ON SHEET A-003R:
 A. FENESTRATION PRODUCT APPROVALS (ENTRY DOORS).
 B. ROOFING PRODUCT APPROVALS AND ENHANCED NAILING IF
 REQUIRED.
 C. SEPARATE PERMIT FOR GENERATOR AND STAND.
 D. SEPARATE PERMITS FOR LOW VOLTAGE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  