| Plan Review Notes For Permit 18100337 |
| Permit Number |
18100337 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-15 10:09:08 | 1) SUBMIT TWO COPIES OF A SITE PLAN SHOWING THE | | | LOCATION OF THE SLAB / PUMPS.FBC SECS. 107.1, | | | 107.3.5.1. | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PUMPS.FBC SEC. 107.2.1. | | | 3) SUBMIT ANCHORING DETAILS FOR THE PUMPS. INDICATE | | | TYPE, LENGTH, NUMBER & DIAMETER OF THE FASTENERS. FBC | | | 107.2.1. | | | 4) SHOW THE TYPE AND SIZE OF ALL PIPE ON THE | | | DRAWING.FBC 107.2.1. | | | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE ALUMINUM HOUSING. | | | 6) A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL | | | BOOSTER PUMPS IN ACCORDANCE WITH THE 2017 FBC-PLUMBING | | | SEC.606.5.5. | | | 7) SUBMIT DETAILS FOR THE SUPPORTING OF THE PIPE. | | | COMPLY WITH 2017 FPC-PLUMBING TABLE 308.5. | | | 8) INDICATE ON THE PLANS IF YOU ARE REPLACING EXISTING | | | PUMPS OR ADDING NEW PUMPS TO AN EXISTING DOMESTIC WATER | | | SYSTEM, PRESSURE REDUCING VALVES WILL BE REQUIRED IF | | | THE WATER PRESSURE WITHIN THE BUILDING EXCEEDS 80 PSI | | | STATIC PRESSURE. VALVES SHALL COMPLY WITH 2017 | | | FBC-PLUMBING SEC.604.8. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|