| Plan Review Notes For Permit 18100307 |
| Permit Number |
18100307 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-24 15:31:15 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- CALCULATED DESIGN PRESSURES SUBMITTED ARE INCORRECT. | | | ACCORDING TO PLANS ON CITY RECORDS. OPENINGS #1 AND #7 | | | ARE LOCATED IN END ZONE NOT INTERIOR ZONE. REVISE AS | | | REQUIRED. NOTE: ACCORDING TO NOTE "A" ON FIGURE | | | R301.2(7) FBC-RESIDENTIAL END ZONE APPLIES TO OPENINGS | | | WITHING 4'-0" IN ALL CASES. REVISE AS REQUIRED. | | | | | | 2- CLEARLY SPECIFY SIZE OF OPERABLE WINDOWS ON MASTER | | | BEDROOM WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS | | | REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|