| Date |
Text |
| 2018-11-06 11:35:16 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | THERE ARE SOME QUESTIONS WITH THE SUBMITTALS THAT NEED |
| | TO BE ADDRESSED. |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) IT IS DIFFICULT TO CORRELATE SOME OF THE EXTERIOR |
| | CLADDING SUBMITTALS WITH THE PLANS. PROVIDE |
| | CLARIFICATION AS TO WHERE EACH OF THE PRODUCTS WILL BE |
| | USED AND THE SPECIFIC APPLICATION OF THE PRODUCT. FBC |
| | 107.2.1 |
| | |
| | 2) THE EXPANDED POLYSTYRENE BOARD LISTING INFORMATION |
| | IS MISSING PAGE 2. FBC 107.2.1 |
| | |
| | 3) THE ARCHITECT'S SHOP DRAWING REVIEW STAMP OBSCURES |
| | SOME OF THE INFORMATION ON SOME OF THE SUBMITTAL |
| | DOCUMENTS. FBC 107.2.1 |
| | |
| | 4) THE HILTI FASTENER CHARTS ON PAGES 73,74 AND 75 OF |
| | THE CLARK DIETRICH CALCULATIONS ARE ILLEGIBLE. FBC |
| | 107.2.1 |
| | |
| | 5) THE ELEVATIONS APPEAR TO SHOW FAUX STONE AND FAUX |
| | WOOD PANELS ON THE COLD FORMED STEEL BUILT OUT SECTIONS |
| | ON THE EXTERIOR WALLS. THE COLD FORMED STEEL FRAMING |
| | COMPUTATIONS SHOW A TOTAL WALL DEAD LOAD OF 18 PSF FOR |
| | THE WALLS WHICH INCLUDES THE 5/8" GYP. BOARD, ONE INCH |
| | OF STUCCO AND THE FRAMING. IT DOES NOT INCLUDE THE DEAD |
| | WEIGHT OF THE INSTALLED VENEER UNITS WHICH CAN BE AS |
| | MUCH AS 15 PSF PER SECTION 3.0 DESCRIPTION ON ESR-1215 |
| | OF THE EVALUATION REPORT. FBC 1604.1 |
| | |
| | 6) THE EVALUATION REPORT FOR THE ELDORADO STONE |
| | ADDRESSES DEFLECTION BUT DOES NOT INDICATE THE |
| | ALLOWABLE DESIGN WIND PRESSURES FOR THE ATTACHMENT OF |
| | THE PRODUCT TO THE STUCCO BASE. ACCORDING TO THE |
| | ELEVATIONS THIS FAUX STONE WILL BE USED IN WALL ZONES |
| | 4, 5, 4P AND 5P. THE COMPONENT AND CLADDING CHARTS ON |
| | SHEET S-1.11 HAVE NEGATIVE PRESSURES AS HIGH AS -98 PSF |
| | IN WALL ZONE 5 AND -161 PSF IN ZONES 4P AND 5P AT THE |
| | PARAPET WALLS. FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 7) THE ELDORADO STONE, "VINTAGE RANCH" PRODUCT IS NOT |
| | ONE OF THE PATTERNS LISTED ON PAGE 3 OF ESR-1215. |
| | PROVIDE PRODUCT APPROVALS FOR THE VILLAGE RANCH |
| | CLADDING. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. |
| | |
| | 8) PROVIDE PRODUCT APPROVALS OR ENGINEERED CALCULATIONS |
| | TO SHOW THAT THE STEEL FRAMED BUILT OUT SECTIONS WITH |
| | THE DENS GLASS, WIRE LATH, STUCCO AND FAUX STONE |
| | ASSEMBLY WILL WITHSTAND THE WIND LOADS SPECIFIED ON THE |
| | STRUCTURAL DRAWINGS. FBC 1604.1 |
| | |
| | 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |