| Plan Review Notes For Permit 18100288 |
| Permit Number |
18100288 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-15 13:34:55 | 1) THE HANDICAPPED STALL DOOR IN THE MEN'S STAFF LAV | | | CANNOT SWING INTO THE MINIMUM REQUIRED COMPARTMENT | | | AREA. 2017 FBC-ACCESS. SECS.604.8.1.2. | | | 2) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE | | | HANDICAPPED ACCESSIBLE DRINKING FOUNTAINS ON THE PLANS. | | | 3) SUBMIT A DEMO PLAN FOR REVIEW. CLEARLY SHOW WHAT IS | | | EXISTING TO REMAN IN AND WHAT IS BEING REMOVED. FBC | | | 107.2.1. | | | 4) SHT. A 700 - THE FINISH SCHEDULE NOTES THE TYPE OF | | | FLOORING IN THE MEN'S & WOMEN'S LAVS, THE MEN'S & | | | WOMEN'S STAFF LAVS AND THE JANITOR SINK TO BE CARPET | | | TILE. THE FLOORS IN THESE AREAS SHALL COMPLY WITH 2017 | | | FBC SEC. 1210.2.1. | | | 5) SHOW THE INSIDE FINISHED DIMENSIONS (LXW) OF EACH | | | TOILET COMPARTMENT AND TOILET ROOM. 2017 FBC SECS. | | | 107.2.1, 2017 FBC-ACCESS. SEC 604.8.1.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|