| Date |
Text |
| 2019-03-01 16:35:13 | RESIDENTIAL (R3)ALTERATION/ADDITION THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | NOTE 1: NEED ZONING APPROVAL |
| | |
| | |
| | NOTE 2: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE |
| | ENERGY CALCULATIONS ARE PROPERLY SIGNED BY OWNER OR |
| | AUTHORIZED AGENT AND THE NAME OF THE PERSON PREPARING |
| | THEM IS PROVIDED. PROVISO MEANS CONTRACTOR WILL SUBMIT |
| | REQUIRED INFORMATION AFTER THE PERMIT IS ISSUED BUT |
| | BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION |
| | FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | |
| | |
| | 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE |
| | APPROVED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 1106 FBC-EXISTING BUILDING. |
| | NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO |
| | AVOID CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE |
| | CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY |
| | DESIGNATED AGENT PRIOR TO RECEIVE THE PERMIT AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 6TH EDITION (2017). |
| | |
| | B) PROVIDE THE NAME OF THE PERSON DOING THE |
| | CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS |
| | JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) ITEM #9 IS INCOMPLETE. NEED TO PROVIDE INFORMATION |
| | FOR ADJACENT WALL BETWEEN GARAGE AND THE MAIN HOUSE A/C |
| | AREA. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4 |
| | DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE |
| | RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. |
| | OR, PROVIDE COMPLETE DOCUMENTATION SHOWING COMPLIANCE |
| | WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON |
| | SEC. R806.2. |
| | |
| | G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| | PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH |
| | GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO. |
| | OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | H)PROVIDE WINDOWS AND DOORS MANUFACTURER'S |
| | SPECIFICATIONS SHOWING THE SHGC FACTOR SPECIFIED ON THE |
| | ENERGY CALCULATIONS ON ITEM #7 AS REQUIRED BY SEC. |
| | R405.4.3 FBC-ENERGY CONSERVATION. |
| | |
| | ORIGINAL COMMENT: |
| | 3- DRAINAGE |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | RESPONSE: |
| | DRAINAGE PLAN PROVIDED NOW DOESN'T SHOW ANY DRAINAGE |
| | PLAN SHOWING HOW THE WATER IS DIVERTED TO ANY APPROVED |
| | POINT OF COLLECTION AS REQUIRED BY SEC. R401.3. THERE |
| | IS A NOTE STATING "SLOPE GRADE 1/4" PER FOOT". THIS |
| | INFORMATION IS INSUFFICIENT. SLOPE GRADE TOWARDS |
| | WHERE?. WATER CAN NOT BE DIVERTED TO THE NEIGHBORS AND |
| | IT HAS TO BE DIVERTED AWAY FROM THE FOUNDATION. REVISE |
| | AS REQUIRED. |
| | |
| | 4- SHEET A-2.2: |
| | A) OK. |
| | |
| | B)OK. |
| | |
| | C) OK. |
| | |
| | D) OK |
| | |
| | E) OK |
| | |
| | F) OK. |
| | |
| | G) OK. |
| | |
| | H) OK |
| | |
| | 5- OK. |
| | |
| | 6- OK. |
| | |
| | 7- SHEET A-2.0: |
| | A) OK. |
| | |
| | B) OK |
| | |
| | C)OK. |
| | |
| | 8- OK. |
| | |
| | 9- OK. |
| | |
| | 10- OK. |
| | |
| | 11- OK. |
| | |
| | 12- OK. |
| | |
| | 13- OK. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A)OK |
| | |
| | B) OK |
| | |
| | C) OK |
| | |
| | D)OK. |
| | |
| | 15- OK. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |