| 2018-10-30 08:00:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL NOTES SAY THE ADDIDTION WILL BE DONE TO |
| | THE 2011 NATIONAL ELECTRIC CODE. 2014 IS THE CURRENT |
| | NATIONAL ELECTRICAL CODE AND IS THE APPLICABLE CODE FOR |
| | THIS PROJECT. PROVIDE CORRECTION. FBC 107.2.1 |
| | |
| | 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS |
| | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 |
| | |
| | 3. LOAD CALCULATION IS NOT ACCURATE. PROVIDE ACCURATE |
| | LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE |
| | E3602.2 |
| | |
| | 4. MISSING RECEPTACLE RIGHT OF EXTERIOR DOOR IN NEW |
| | MASTER BEDROOM. 210.52A1 NEC |
| | |
| | 5. MISSING RECEPTACLE RIGHT OF CLOSET DOOR IN NEW |
| | MASTER BEDROOM. 210.52A1 NEC |
| | |
| | 6. SMOKE/CARBON COMBO ALARM REQUIRED OUTSIDE BEDROOMS |
| | (NEW AND EXISITING) DUE TO NEW PROPOSED ATTACHED |
| | GARAGE. FBC R314 & 315 |
| | |
| | 7. RECEPTACLE REQUIRED IN GARAGE. 210.52G1 |
| | |
| | 8. ALL RECEPTACLES IN GARAGE MUST BE GFCI PROTECTED. |
| | 210.8A2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |