| 2019-01-15 11:31:37 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS |
| | SHALL BE INSTALLED FOR KITCHEN COUNTER TOP RECEPTACLES. |
| | PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2 |
| | 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE SQUARE FOOTAGE CALCULATION ON |
| | PLAN IS ONLY FOR 393 SQUARE FEET, WHICH DOES NOT AGREE |
| | WITH THE SQUARE FOOTAGE SHOWN ON PBC PAPA. NEC 215.2, |
| | 220, 408.30; FBC RE E3602.2 |
| | 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB |
| | FBC 107.2.1; NEC 230.2; FBC RE E3601.2 |
| | 6. IF NEW SERVICE IS PROPOSED, PROVIDE DETAILS OF |
| | EXISTING AND PROPOSED. PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR EACH PANEL INCLUDING INFORMATION FROM |
| | THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT |
| | CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE |
| | STATED AIC RATING OF THE SERVICE EQUIPMENT AND |
| | DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 7. A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE |
| | DWELLING UNIT. PROVIDE CORRECTION. FBC RE R314.3 |
| | 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 9. GFCI PROTECTION IS REQUIRED FOR ALL EXTERIOR |
| | RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC 210.8; FBC |
| | RE E3902.3 |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 11. THERE APPEARS TO BE SOMETHING LOCATED IN FRONT OF |
| | ELECTRICAL PANEL. CLEARANCE IN FRONT OF THE PANEL IS |
| | REQUIRED. PROVIDE CORRECTION.NEC 110.26; FBC RE E3405.1 |
| | 12. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| | FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | |
| | |
| | |