| 2019-01-02 15:23:09 | CONTRACT EMAILED, VALUE IS CORRECT. 1/2/19 |
| | |
| | |
| 2018-12-20 08:48:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 |
| | (NOT PROVIDED) |
| | 2. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS |
| | SHALL BE INSTALLED FOR KITCHEN COUNTER TOP RECEPTACLES. |
| | PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2 |
| | 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE SQUARE FOOTAGE CALCULATION ON |
| | PLAN IS ONLY FOR 393 SQUARE FEET, WHICH DOES NOT AGREE |
| | WITH THE SQUARE FOOTAGE SHOWN ON PBC PAPA. NEC 215.2, |
| | 220, 408.30; FBC RE E3602.2 |
| | 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB |
| | FBC 107.2.1; NEC 230.2; FBC RE E3601.2 |
| | 6. IF NEW SERVICE IS PROPOSED, PROVIDE DETAILS OF |
| | EXISTING AND PROPOSED. PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR EACH PANEL INCLUDING INFORMATION FROM |
| | THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT |
| | CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE |
| | STATED AIC RATING OF THE SERVICE EQUIPMENT AND |
| | DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 7. A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE |
| | DWELLING UNIT. PROVIDE CORRECTION. FBC RE R314.3 |
| | 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 9. GFCI PROTECTION IS REQUIRED FOR ALL EXTERIOR |
| | RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC 210.8; FBC |
| | RE E3902.3 |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 11. THERE APPEARS TO BE SOMETHING LOCATED IN FRONT OF |
| | ELECTRICAL PANEL. CLEARANCE IN FRONT OF THE PANEL IS |
| | REQUIRED. PROVIDE CORRECTION.NEC 110.26; FBC RE E3405.1 |
| | 12. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| | FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |