Date Text
2019-01-31 11:36:27RESIDENTIAL (R3)ALTERATION/ADDITION SECOND REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES - CONVERSION OF PORCH TO BEDROOM. PLANS
 REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL (561)
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN SET
 AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED
 STAMPED AND WITH A COPY OF THE RECEIPT AS APPLICABLE.
 PLEASE PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE
 FORM TO THE PBC IMPACT FEE OFFICE. THE FORM CAN BE
 FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION
 /PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 RESPONSE:
 NEED TO PROVIDE COPY OF PAID RECEIPT ALSO. ONLY THE
 COUNTY STAMPED PLAN WAS SUBMITTED.
  
  
 ORIGINAL COMMENT:
 2- NONE OF THE WINDOWS OF THE NEW BEDROOM COMPLY WITH
 THE EGRESS REQUIREMENTS. OF SEC. R310.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED TO COMPLY.
  
 RESPONSE:
 REPEAT COMMENT. 36"X52" S.H . WINDOWS DON'T COMPLY WITH
 EGRESS REQUIREMENTS. THIS WINDOW SIZE DOESN'T COMPLY
 WITH THE MIN. CLEAR HEIGHT. EGRESS WINDOWS NEED TO
 COMPLY WITH ALL CLEAR DIMENSIONS FOR WIDTH, HEIGHT AND
 TOTAL OPENING AREA. SEE SEC. R310.2.1 FBC-RESIDENTIAL.
  
 3- OK.
  
 4- OK.
  
 5- OK.
  
 6- WALL SECTION 2/A-1:
 A) OK.
  
 ORIGINAL COMMENT:
 B) SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 AND R806.2 FBC-RESIDENTIAL.
 NOTE: ONLY CONTINUOUS VENT WILL PROVIDE CROSS
 VENTILATION. ALSO, COORDINATE WITH THE ENERGY
 CALCULATIONS. NEED 1/150 VENT RATIO. SEE COMMENTS ON
 ENERGY CALCULATIONS.
  
 RESPONSE:
 DESIGNER OF RECORD NEEDS TO SPECIFY SIZE OF CONTINUOUS
 VENTILATION.
  
 C)OK.
  
 ORIGINAL COMMENT:
 D) SHOW THE 6" MIN. CLEARANCE FOR TERMITE INSPECTION AS
 REQUIRED BY SEC. R318.7 FBC-RESIDENTIAL.
  
 RESPONSE:
 SEE SEC. R318.7. NEED TO SPECIFY THE 6" CLEARANCE
 BETWEEN THE EXTERIOR WALL COVERING AND FINAL EARTH
 GRADE.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) OK.
  
 B)OK.
  
 8- OK.
  
 9- ENERGY CALCULATIONS:
 A) OK.
  
 B) OK.
  
 C)OK.
  
 D)OK.
  
 E)
  
 F) OK.
  
 G) OK.
  
 ORIGINAL COMMENT:
 H) ITEM #15 ON PAGE 1 OF 5 IS TAKEN THE CEILING FAN AND
 WHOLE HOUSE FAN OPTION. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOSE COMPLIES WITH BOTH
 CREDITS. SEE SEC. R405.7.5 AND SEC. R405.7.6 FBC-ENERGY
 CONSERVATION FOR SPECIFIC REQUIREMENTS.
  
 RESPONSE:
 ENERGY CALCULATIONS ARE NOW TAKING THE CROSS
 VENTILATION CREDIT. IT LOOKS LIKE THE ADDITION DOESN'T
 COMPLY WITH THE REQUIREMENTS OF SEC. R405.7.4
 FBC-ENERGY CONSERVATION. SEE ITEM 1 OF SEC. R405.7.4.
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 I) SPACES SHOWN ON PAGE 2 OF 5 ARE NOT CLEAR. FLOOR
 PLANS DON'T SHOW ANY SUNSPACE, NUMBER OF BEDROOMS IS
 NOT CLEAR. COORDINATE WITH ITEM #3 ABOVE. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENERGY CALCULATIONS WERE REVISED TO SHOW COMPLIANCE
 ONLY FOR THE BEDROOM ADDITION. REVISED CALCULATIONS
 SPECIFY THAT THERE IS A KITCHEN IN THE BEDROOM. THIS IS
 INCORRECT. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 J) ENGINEER PREPARING THE ENERGY CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER 471 F.S.
 AND 61G15-23.001 FAC WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
  
 RESPONSE:
 FRONT PAGE WHERE ENGINEER SIGNED AND PROVIDED HIS NAME
 IS MISSING THE ENGINEER'S LICENSE NUMBER.
  
 K)OK.
  
 ORIGINAL COMMENT:
 L)DOORS INFORMATION ON PAGE 3 OF 5 IS NO CLEAR. SHOW ON
 PLANS THE SPECIFIED WOOD DOORS. SEC. R101.5.1.1.2
 FBC-RESIDENTIAL.
 NOTE: DOORS TO BE CONSIDERED ARE ONLY FOR EXTERIOR
 DOORS OR THE DOORS SEPARATING THE NON-A/C AREAS TO A/C
 AREAS.
  
 RESPONSE:
 THERE ARE NOT EXTERIOR DOORS IN THE BEDROOM ADDITION.
 REVISE AS REQUIRED. THE DOOR FROM THE BEDROOM TO THE
 REST OF THE HOUSE IS WITHIN A/C AREA. NO NEED TO
 INCLUDE IT. THIS AREA IS NOT PART OF THE EXTERIOR
 ENVELOPE. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 M) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE EXCEPTION OF SEC. R806.2
 FBC-RESIDENTIAL WHEN SPECIFYING A VENT RATIO OF 1/300
 AS SHOWN ON PAGE 3 OF 5.
  
 RESPONSE:
 VENTILATION SHOWN ON PLANS DON'T COMPLY WITH THE
 REQUIREMENTS OF THE EXCEPTION TO SEC. R806.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
 10- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  