2018-11-06 12:09:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DUE TO THE COMPLEXITY OF THE PROJECT, THE PLUMBING
 PIPING PLAN REQUIRES MORE INFORMATION. PROVIDE 1ST AND
 2ND FLOOR PLAN PLUMBING LAYOUT IN PLAN VIEW. SHOW WHICH
 WALLS THE SANITARY RISERS TO THE SECOND FLOOR WILL BE
 LOCATED. PLAN VIEWS AND RISER DIAGRAM SHALL MATCH. WPB
 FBC 107.2.1
 2. RE: PLAN SHEET A2; SANITARY RISER DIAGRAM
 A. PLEASE PROVIDE A DIRECTIONAL ORIENTATION SO THAT THE
 DIAGRAM CORRESPONDS WITH THE PLAN VIEW. WPB FPC 107.2.1
 B. PLEASE IDENTIFY BATHROOMS. WPB FBC 107.2.1
 C. CONNECT CLOTHES WASHER FIXTURE DRAIN TO A VERTICAL
 DRAIN IN THE WALL BEFORE CONNECTING UNDERGROUND TO
 COMPLY WITH FBC PL 802.3.3 (SEE FBC RES P2601.1) AND
 PROVIDE INDIVIDUAL VENT PER FBC RES P3102.2.1.
 D. NUMEROUS LAVATORY AND SINK FIXTURE DRAINS THROUGHOUT
 THE PROJECT DROP VERTICALLY BEFORE CONNECTING TO THE
 VENT. THE TOTAL FALL IN A FIXTURE DRAIN DUE TO PIPE
 SLOPE SHALL NOT EXCEED THE DIAMETER OF THE FIXTURE
 DRAIN, NOR SHALL THE VENT CONNECTION TO A FIXTURE
 DRAIN, EXCEPT FOR WATER CLOSETS, BE BELOW THE WEIR OF
 THE TRAP PER FBC RES P3105.2. CORRECT AND RESUBMIT
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  