Plan Review Notes
Plan Review Notes For Permit 18100243
Permit Number 18100243
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-24 11:28:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT
 IS TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10; FBC RE E3606.3
 2. AFCI PROTECTION SHOWN IN NOTE 10A ON SHEET E3 IS NOT
 CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 5. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING THE 400 AMP
 METER FROM THE POWER COMPANY. SERVICE CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY OF NOT LESS THAN 83% OF
 THE SERVICE RATING. THE WIRE SIZE SPECIFIED IS ONLY
 RATED FOR 175 AMPS INSTEAD OF THE 332 AMPS REQUIRED.
 PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC
 RE E3603.1.1
 6. RISER DIAGRAM SHOWS 4/0 COPPER FEEDING THE TRANSFER
 SWITCH FROM THE METER CAN. SERVICE CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY OF NOT LESS THAN 83% OF
 THE SERVICE RATING. THE WIRE SIZE SPECIFIED IS ONLY
 RATED FOR 230 AMPS INSTEAD OF THE 332 AMPS REQUIRED.
 PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC
 RE E3603.1.1
 7. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING PANEL 1 FROM
 THE TRANSFER SWITCH. FEEDER CONDUCTORS ARE REQUIRED TO
 HAVE AN AMPACITY EQUAL OR GREATER THAN THE PANEL BEING
 FED. THE WIRE SIZE SPECIFIED IS ONLY RATED FOR 175 AMPS
 INSTEAD OF THE 200 AMPS REQUIRED. PROVIDE CORRECTION.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1.2
 8. RISER DIAGRAM SHOWS 2/0 COPPER FEEDING TRANSFER
 SWITCH FROM THE GENERATOR. FEEDER CONDUCTORS ARE
 REQUIRED TO HAVE AN AMPACITY EQUAL OR GREATER THAN THE
 PANEL BEING FED. THE WIRE SIZE SPECIFIED IS ONLY RATED
 FOR 175 AMPS INSTEAD OF THE 200 AMPS REQUIRED. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1.2
 9. PANELS 1 AND 2 ARE SHOWN AS MAIN LUG ONLY PANELS. IF
 THE INTENT IS TO TAP OFF THE 400 AMP MAIN IN THE
 TRANSFER SWITCH, THE TAP MUST TERMINATE IN A MAIN
 BREAKER. PROVIDE CORRECTION. NEC 215.3, 240.21
 10. PROVIDE SPEC SHEET FOR 400 AMP TRANSFER SWITCH. IS
 THIS SERVICE ENTRANCE RATED? IS THERE ONE 400 AMP
 BREAKER AS THE MAIN IN THIS TRANSFER SWITCH? WPB FBC
 107.2.1; NEC 110.3; FBC RE E3403.3
 11. POOL PUMP, SPA PUMP, AND SPA BLOWER REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 680.21(C), 680.44;
 FBC RE E4203.1.3, E4208.1
 12. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 13. LOCATION OF POOL PANEL DOES NOT MEET REQUIREMENTS
 FOR CLEARANCE. PROVIDE CORRECTION. NEC 110.26; FBC RE
 E3405.1
 14. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  