Plan Review Notes
Plan Review Notes For Permit 18100242
Permit Number 18100242
Review Stop P
Sequence Number 1
Notes
Date Text
2018-11-06 10:57:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DUE TO THE COMPLEXITY OF THE PROJECT, THE PLUMBING
 PIPING PLAN REQUIRES MORE INFORMATION. PROVIDE 1ST AND
 2ND FLOOR PLAN PLUMBING LAYOUT IN PLAN VIEW. SHOW WHICH
 WALLS THE SANITARY RISERS TO THE SECOND FLOOR WILL BE
 LOCATED. PLAN VIEWS AND RISER DIAGRAM SHALL MATCH. WPB
 FBC 107.2.1
 2. RE: PLAN SHEET A10; SANITARY RISER DIAGRAM
 A. PLEASE PROVIDE A DIRECTIONAL ORIENTATION SO THAT THE
 DIAGRAM CORRESPONDS WITH THE PLAN VIEW. WPB FPC 107.2.1
 B. PLEASE IDENTIFY BATHROOMS. WPB FBC 107.2.1
 C. PROVIDE INDIVIDUAL VENT FOR CLOTHES WASHER FIXTURE
 DRAIN.FBC RES P3102.2.1
 D. LAVATORY FIXTURE DRAINS IN BATH #4 CLOSEST TO THE
 WATER CLOSET, THE MASTER BATH AND BOTH HALF BATHS DROP
 VERTICALLY BEFORE CONNECTING TO THE VENT. THE TOTAL
 FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE SHALL NOT
 EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR SHALL THE
 VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR WATER
 CLOSETS, BE BELOW THE WEIR OF THE TRAP PER FBC RES
 P3105.2. CORRECT AND RESUBMIT
 E. A LAVATORY IN THE MASTER BATH IS NOT SHOWN. INCLUDE
 ON RESUBMITTED DIAGRAM. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER