| 2018-11-09 16:40:36 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18100242 |
| | REVIEWED: NOVEMBER 9, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | [FBC R322.2.1]THE CITY OF WPB HAS ADOPTED A 2? |
| | FREEBOARD ABOVE B.F.E. SEE AMENDMENT TO FBC R322.2.1 IN |
| | ORD. NO. 4765-18, ? 2, 3-12-2018(SEC 18-33) |
| | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS |
| | AE WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY |
| | OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN |
| | ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN |
| | FLOOD ELEVATION (DFE) TO BE 9.0 FEET. PLEASE NOTE THIS |
| | INFORMATION ON YOUR PLANS. |
| | |
| | 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. |
| | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS |
| | SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD. |
| | ALLSO, UPDATE SURVEY AND SIRE PLAN TO SHOW LOWEST FLOOR |
| | ELEVATION OF 9 FT. GARAGE CAN BE LOWER WITH FLOOD VENTS |
| | AS SHOWN ON PLANS. |
| | |
| | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED |
| | FLOOR ELEVATION IS RECOMMENDED. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | |
| | 2. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| | CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| | AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND |
| | ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION |
| | CONTROL |
| | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| | /FORMS,-PERMITS-APPLICATIONS |
| | |
| | 3. [FBC 107.5][FBC 110.9][FBC R401.3]PROVIDE SITE |
| | DRAINAGE PLAN. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 4. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | 5. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD |
| | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 6. SEPARATE PERMIT WILL BE REQUIRED FOR FENCE/WALL, |
| | DRIVEWAY(ENGINEERING DEPARTMENT), POOL AND GENERATOR. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |