| Plan Review Notes For Permit 18100232 |
| Permit Number |
18100232 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-23 10:41:03 | 1) PLACE A NOTE ON THE PLANS THAT THE GENERATOR EXHAUST | | | SHALL BE LOCATED A MINIMUM OF 10 FT. FROM BUILDING | | | OPENINGS OR AS PER MANUF. INSTALLATION MANUAL. | | | 2) THE ORIGINAL GAS PLAN ON FILE IN THE CITY RECORDS | | | SHOWS THE LONGEST RUN AT 100 FEET. THIS DISTANCE SHALL | | | BE USED IN THE SIZING OF ALL THE GAS PIPING. 2017 | | | FBC-FUEL GAS SEC. 402.4.1, NOT 15 FEET. | | | 3) THE MINIMUM SIZE METALLIC PIPE AT THE OUTLET OF THE | | | GAS METER SHALL BE 1 1/2 INCHES FOR A LESS THAN 2 PSI | | | SYSTEM ACCORDING TO TABLE 402.4 (2) OF THE 2017 | | | FBC-FUEL GAS CODE. | | | 4) THE MINIMUM SIZE OF THE PE PIPE SHALL BE 1 1/4 INCH | | | PER TABLE 402.4 (21) OF THE 2017 FBC-FUEL GAS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|