| Plan Review Notes For Permit 18100224 |
| Permit Number |
18100224 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-11-29 06:55:48 | PLEASE SEE COMMENTS BELOW AND ATTACHMENT FROM TRACY | | | WARD, SENIOR STORMWATER ENGINEER, ENGINEERING SERVICES, | | | 561-494-1120: | | | | | | SHEET C-1: PLEASE LABEL VERTICAL DATUM & PROVIDE | | | CONVERSION EQUATION TO NGVD '29. | | | SHEET C-2: PLEASE PROVIDE CONVERSION EQUATION TO NGVD | | | '29. | | | SHEET C-3: PLEASE REVISE STORMWATER CALCULATIONS PER | | | ATTACHMENT. (ENVIRONMENTAL RESOURCE PERMIT INFORMATION | | | MANUAL, PT. III - REFERENCES & DESIGN AIDS, SECTION U - | | | DESIGN EXAMPLE FOR EXFILTRATION TRENCH & MARKUP OF | | | SHEET U-6) | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|