| 2018-10-22 10:12:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18100210 |
| | 10/22/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PRIMARY PERMIT FOR THIS PROJECT LISTED ON THE |
| | APPLICATION WAS FOR A NEW MERCANTILE TENANT OCCUPANCY- |
| | GYPSY SURF- PERMIT #18020938. PLEASE PROVIDE A REVISED |
| | FLOOR PLAN TO SHOW THE LOCATION OF THE NEW PIZZA OVEN |
| | AND EXHAUST SYSTEM. |
| | |
| | 2) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS OR A |
| | PRODUCT DATA SHEET FOR THE WOOD FIRED PIZZA OVEN TO |
| | VERIFY THE APPLIANCE IS LISTED AND LABELED IN |
| | ACCORDANCE WITH UL 2162- SEE SECTION 917.1 FBC M. |
| | |
| | 3) INDICATE HOW MAKEUP AIR IS BEING PROVIDED PER |
| | SECTION 508.1 AND PROVIDE AN AIR BALANCE CALCULATION- |
| | SECTION 508.1.2 FBC M. |
| | |
| | 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE EXHAUST FAN AND WALL BRACKET- SECTION 301.15 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |