2018-10-16 09:41:20BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH.
  
 2- PROVIDE SKETCH SHOWING AREAS OF WORK AND SQUARE
 FOOTAGE. SEC. 107.2.1 CITY AMENDMENTS.
  
  
  