| Notes |
| Date |
Text |
| 2018-10-06 11:37:05 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING | | | SUBMITTALS: | | | 1. FBC 107; FLOOR PLAN WITH DIMENSIONS AND LOCATION OF | | | WORK. | | | 2. FBC 107; PROPOSED UNDERLAYMENT. | | | 3. FBC; 720.2 FLAME SPREAD TEST REPORTS FOR THE | | | PROPOSED UNDERLAYMENT BASED ON THE EXISTING SITE | | | CONDITIONS. | | | (FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE | | | DEVELOPED INDEX OF NOT MORE THAN 450.) | | | 4. FBC 107; ALL DOCUMENTS SHALL BE SUBMITTED IN | | | DUPLICATE. | | | |
|