| 2018-11-06 13:22:12 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW ALL PLUMBING FIXTURES A CHANGE OF OCCUPANCY |
| | SHALL COMPLY WITHE FBC EXISTING BUILDING 1010.1 |
| | INCREASED DEMAND.WHERE THE OCCUPANCY OF AN EXISTING |
| | BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED |
| | SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO INCREASED OR |
| | DIFFERENT PLUMBING FIXTURE REQUIREMENTS OR TO INCREASED |
| | WATER SUPPLY REQUIREMENTS IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING, THE NEW OCCUPANCY |
| | SHALL COMPLY WITH THE INTENT OF THE RESPECTIVE FLORIDA |
| | BUILDING CODE, PLUMBING PROVISIONS. |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC EXISTING BUILDING |
| | 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | |
| | 3. IN COMPILING WITH THE OTHER TRADES IT MAY BE |
| | NECESSARY TO COMPLY WITH FBC ACC 202.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |