Plan Review Notes
Plan Review Notes For Permit 18100183
Permit Number 18100183
Review Stop P
Sequence Number 1
Notes
Date Text
2018-11-06 13:22:121ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW ALL PLUMBING FIXTURES A CHANGE OF OCCUPANCY
 SHALL COMPLY WITHE FBC EXISTING BUILDING 1010.1
 INCREASED DEMAND.WHERE THE OCCUPANCY OF AN EXISTING
 BUILDING OR PART OF AN EXISTING BUILDING IS CHANGED
 SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO INCREASED OR
 DIFFERENT PLUMBING FIXTURE REQUIREMENTS OR TO INCREASED
 WATER SUPPLY REQUIREMENTS IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING, THE NEW OCCUPANCY
 SHALL COMPLY WITH THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC EXISTING BUILDING
 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 3. IN COMPILING WITH THE OTHER TRADES IT MAY BE
 NECESSARY TO COMPLY WITH FBC ACC 202.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  