Plan Review Notes
Plan Review Notes For Permit 18100183
Permit Number 18100183
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-18 12:05:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLAD SHEETS DOES NOT PROVIDE
 SUFFICIENT INFORMATION TO DETERMINE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
  
 2) PLEASE PROVIDE THE TYPE OF DAY-CARE BEING PROPOSED
 INCLUDING THE NUMBER OF PROPOSED CLIENTS AND AGES.
  
 PER NFPA 1, OCCUPANCY FIRE SAFETY
  
 20.3 DAY-CARE OCCUPANCIES.
 20.3.1 APPLICATION. NEW AND EXISTING DAY-CARE
 OCCUPANCIES SHALL
 COMPLY WITH SECTION 20.3 AND NFPA 101.
 20.3.1.1 IN NEW DAY-CARE OCCUPANCIES, WHERE A FACILITY
 HOUSES
 MORE THAN ONE AGE GROUP OR SELF-PRESERVATION
 CAPABILITY, THE
 STRICTEST REQUIREMENTS APPLICABLE TO ANY GROUP PRESENT
 SHALL APPLY
 THROUGHOUT THE DAY-CARE OCCUPANCY OR BUILDING, AS
 APPROPRIATE TO
 A GIVEN AREA, UNLESS THE AREA HOUSING SUCH A GROUP IS
 MAINTAINED
 AS A SEPARATE FIRE AREA.
  
 20.3.1.4 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS
 PRIMARILY
 EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER,
 EVEN THOUGH
 THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL
 AGE, SHALL
 COMPLY WITH THE PROVISIONS OF CHAPTER 14 OR CHAPTER 15
 OF NFPA
 101, AS APPLICABLE.
  
 20.3.2.2* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE
 AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS
 SHALL BE SUCH
 THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR
 AREA. [101:
 16.2.2.2.4; 101: 17.2.2.2.4]
 20.3.2.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE BY
 AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO
 THE STAFF.
  
 20.3.4 DAY-CARE HOMES.
 20.3.4.1 CLASSIFICATION.
 20.3.4.1.1 IN NEW DAY-CARE HOMES, THE REQUIREMENTS OF
 20.3.4 SHALL
 APPLY TO DAY-CARE HOMES IN WHICH MORE THAN 3, BUT NOT
 MORE THAN 12,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY, GENERALLY
 WITHIN A DWELLING UNIT.
  
 20.3.4.1.3 IN NEW DAY-CARE HOMES, WHERE A FACILITY
 HOUSES MORE THAN
 ONE AGE GROUP OR ONE SELF-PRESERVATION CAPABILITY, THE
 STRICTEST
 REQUIREMENTS APPLICABLE TO ANY GROUP PRESENT SHALL
 APPLY THROUGHOUT THE
 DAY-CARE HOME OR BUILDING, AS APPROPRIATE TO A GIVEN
 AREA, UNLESS THE
 AREA HOUSING SUCH A GROUP IS MAINTAINED AS A SEPARATE
 FIRE AREA.
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 16.1 GENERAL REQUIREMENTS.
 16.1.1* APPLICATION.
 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE
 OCCUPANCIES. (SEE
 1.3.1.)
 16.1.1.2 ADMINISTRATION. THE PROVISIONS OF CHAPTER 1,
 ADMINISTRATION, SHALL APPLY.
 16.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL
 APPLY.
 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5
 AND
 SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN
 WHICH MORE
 THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY
 OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR
 LESS THAN 24
 HOURS PER DAY.
  
 16.6.1.4 CLASSIFICATION OF OCCUPANCY.
 16.6.1.4.1 SUBCLASSIFICATION OF DAY-CARE HOMES.
 SUBCLASSIFICATION OF
 DAY-CARE HOMES SHALL COMPLY WITH 16.6.1.4.1.1 AND
 16.6.1.4.1.2.
 16.6.1.4.1.1 FAMILY DAY-CARE HOME. A FAMILY DAY-CARE
 HOME
 SHALL BE A DAY-CARE HOME IN WHICH MORE THAN THREE, BUT
 FEWER THAN
 SEVEN, CLIENTS RECEIVE CARE, MAINTENANCE, AND
 SUPERVISION BY OTHER
 THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS
 THAN 24 HOURS PER
 DAY, GENERALLY WITHIN A DWELLING UNIT.
 16.6.1.4.1.2 GROUP DAY-CARE HOME. A GROUP DAY-CARE HOME
 SHALL
 BE A DAY-CARE HOME IN WHICH NOT LESS THAN 7, BUT NOT
 MORE THAN 12,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN
 THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24
 HOURS PER DAY,
 GENERALLY WITHIN A DWELLING UNIT.
  
 PLEASE REVIEW THESE CODES AND ENSURE COMPLAINCE AND
 PROVIDE SUCH DETAILS ON THE RESUBMITTAL.
  
  
  
 3) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
 9.6.1.2 FIRE DETECTION, ALARM, AND COMMUNICATIONS
 SYSTEMS
 INSTALLED TO MAKE USE OF AN ALTERNATIVE PERMITTED BY
 THIS CODE
 SHALL BE CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE
 PROVISIONS
 OF THIS CODE APPLICABLE TO REQUIRED SYSTEMS.
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE
 REQUIREMENTS OF NFPA 70, NATIONAL ELECTRICAL CODE, AND
 NFPA
 72, NATIONAL FIRE ALARM AND SIGNALING CODE, UNLESS IT
 IS AN
 APPROVED EXISTING INSTALLATION, WHICH SHALL BE
 PERMITTED TO BE
 CONTINUED IN USE.
  
 PLEASE PROVIDE PER THE REQUIREMENTS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  