Plan Review Notes
Plan Review Notes For Permit 18100156
Permit Number 18100156
Review Stop R
Sequence Number 1
Notes
Date Text
2018-11-20 12:55:561- FLAT ROOF NOA 17-0222.09 SUBMITTED; CLEARLY MARK
 SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA SUBMITTED. NEED RAS 117 CALCULATIONS
 TO MEET THE DESIGN PRESSURES OF EACH ROOF ZONE AS
 REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
  
  