| 2018-12-19 11:28:21 | 2ND REVIEW FBC-2010 MECHANICAL |
| | REVISION #18100146 |
| | MASTER #15111020 |
| | 12/18/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE- 2010 |
| | FBC M- FLORIDA MECHANICAL CODE- 2010 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE COMMENTS LISTED BELOW ARE REMAINING FROM THE 1ST |
| | REVIEW. PLEASE ADDRESS THEM COMPLETELY |
| | |
| | 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW |
| | CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE |
| | INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED |
| | IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND |
| | MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M. |
| | PLEASE RELOCATE THE CONDENSER TO THE OUTDOORS. |
| | |
| | 2)) M2.24: A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE EXHAUST HOOD. C) INDICATE WHAT COOKING APPLIANCES |
| | WILL BE EXHAUSTED BY THE HOOD- MAKES AND MODELS, TYPE |
| | OF FUEL, AND SUBMIT SPECS. D) PROVIDE A SEQUENCE OF |
| | OPERATION FOR THE SYSTEM. F) PROVIDE SECTION VIEWS |
| | SHOWING THE DUCT CONNECTIONS TO THE HOOD. E) NEW |
| | COMMENT- REFERENCE IS MADE TO ARCHITECTURAL PLANS AND |
| | DETAILS THAT CONTAIN CUSTOM SUPPLY AIR DEVICES. PLEASE |
| | PROVIDE THE PLANS AND DETAILS OR INDICATE WHICH PLAN |
| | SHEET THEY CAN BE FOUND ON. |
| | |
| | 3) M2.26: PROVIDE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK- |
| | SECTION 301.15. |
| | |
| | 4) M2.24: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND |
| | MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5 |
| | (5). PLEASE REMOVE THE DAMPERS AND PROVIDE PROTECTION |
| | FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE |
| | WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |