| 2018-11-05 17:23:12 | 1ST REVIEW FBC-2010 MECHANICAL |
| | REVISION #18100146 |
| | MASTER #15111020 |
| | 11/5/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE- 2010 |
| | FBC M- FLORIDA MECHANICAL CODE- 2010 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.0P1: THE EXTERIOR CONDENSER FOR THE NEW |
| | CARRIER SPLIT SYSTEM CANNOT BE INSTALLED ON THE |
| | INTERIOR OF THE BUILDING BECAUSE IT HAS TO BE INSTALLED |
| | IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING AND |
| | MANUFACTURER'S INSTRUCTIONS- SECTION 304.1 FBC M. |
| | PLEASE RELOCATE THE CONDENSER.TO THE OUTDOORS. |
| | |
| | 2) M2.0P2: RELOCATED PSGF-1A NOT SHOWN. |
| | |
| | 3) M2.24: A) PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | EXHAUST HOOD LISTING MAKE AND MODEL AND DIMENSIONS, AND |
| | SUBMIT MANIFACTURER'S SPECIFICATIONS. B) INDICATE THE |
| | TYPE AND GAGE OF EXHAUST AND MAKEUP AIR DUCT. C) |
| | INDICATE WHAT COOKING APPLIANCE(S) WILL BE EXHAUSTED BY |
| | THE HOOD- MAKE(S) AND MODEL(S), TYPE OF FUEL, AND |
| | SUBMIT SPECS. D) PROVIDE A SEQUENCE OF OPERATION FOR |
| | THE SYSTEM. E) CLARIFY IF A FIRE SUPPRESSION SYSTEM |
| | WILL BE INSTALLED F) PROVIDE SECTION VIEWS SHOWING THE |
| | DUCT CONNECTIONS TO THE HOOD. PLEASE NOTE THAT SEPARATE |
| | PERMITS ARE REQUIRED FOR COMMERCIAL COOKING HOODS AND |
| | FIRE SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | 4) M2.24: WHAT IS THE PURPOSE OF THE FD'S IN THE DUCTS? |
| | HOW WILL THEY FUNCTION? ARE THEY BEING USED FOR |
| | TRANSITIONING TO THE FLAMEBAR DUCTWORK? |
| | |
| | 5) M2.26: PROVIDE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE NEW ROOFTOP FANS AND DUCTWORK- |
| | SECTION 301.15. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |