| Plan Review Notes For Permit 18100146 |
| Permit Number |
18100146 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-22 17:46:34 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E1.01L | | | | | | PLEASE PROVIDE CUT SHEETS FOR WATER FEATURE LIGHTS | | | | | | PAGE E2.27 | | | | | | SYMBOL FOR OUTLETS SHOWN ON ROOF NOT IN LEGEND | | | | | | CIRCUIT LRN 33, 35 NOT SHOWN ON PANEL SCHEDULE.ON PAGE | | | E6.13 | | | | | | CIRCUITS LRN 33, 35 TO BE GFCI PROTECTED | | | | | | PAGE E5.01 | | | | | | PH 24 RISER MSN-4 SIZE OF MAIN TO A1N NOT SHOWN | | | ATS-N, AND ATS-S SIZES NOT SHOWN | | | B1N, AND B1S SIZE NOT SHOWN | | | LRN4 AND LRS4 SIZE NOT SHOWN | | | | | | |
|